Laserfiche WebLink
FOL ~DATION <br /> <br />1. Footings shall bear on firm undisturbed <br />soil. <br /> <br />2, Fills to be used to support footings <br />shall be engineered (report re~ired) or <br />shall be concrete. OI~C 2903-a <br />3. Fc~ndation sections 12"/15"/18" wide, <br />6"/7"/8" thic3~, and 12"/18"/24" depth below <br />natural grade and finish grade are required. <br />OL~C Table 29-a <br /> <br />4. Maximum slopes fc~ ~s~abilized cuts and <br />fills are 2 horizontal to 1 vertical. <br />OUBC 2903- <~) <br />5. Provide underfloor vents of 1~ sq. ft, <br />per 25 lineal ft. of foundation wall. <br />Openillgs to be in at least two walls and <br />near the corners. OL~C 2517-(c)-6 <br />6,, Provide underfloor drainage if space <br />is subject to potential storm or ground- <br />water accumulation. OUBC 2910 <br /> <br />7. Provide reir~orc~nent for concrete <br />walls over A' in height, rain, $~4 bar <br />spaced: horiz, o.c. <br /> reft. o.c. <br />Bars shall be continuous with overlap of <br />min. 10 diameters. One bar 4" ~ bottom <br />and one 4" from top of foundation wall. <br /> <br />8. Extend ~ sill bolts, min. 7" into con- <br />crete. Space max. 6' o.c. and within 12" of <br /> <br />9. Provide min. 18" x 24" access to crawl <br />space, located not over 20' from plumbing <br />cleanouts (OUPC 406-g) or furnace <br />80A-b), Pipes, ducts and other nonstructural <br />construction shall not interfere with ac- <br />ceseability to or within the crawl space. <br />OUBC 2517(c)2 <br /> <br />10. Vapor barriers shall be installed on <br />the grot~ld in crawl spaces and on ~21e warm <br />side of exterior walls. OUBC 5303 (f) 1. d. <br /> <br />11. The required clearance for wood members <br />above grade is 6" for nudsills, 12" for <br />Eirders and 18" for joists. OUBC 2517~c <br />12. All posts to be rm~unted on approved <br />supports. OUBC 2517 (C) 4 <br /> <br />13. Cross bridge or solid block 2" floor <br />joists over 12" in depth every ~8' and solid <br />block at supports. <br /> <br />14. Fire block studwalls and partitions <br />(including furred spaces) at floor, ceiling, <br />soffi~ and a~ mid height of walls over 10' in <br />height and ~ong stair stringers. OL~BC 2517~f <br /> <br />15. Garage door header shall be man <br /> <br />D. F. ~2 with double crioples. <br /> <br />16. Use header, been or rafter sizes noted <br />on the plans. <br /> <br />17. Trusses shall be engineer approval. <br />18. A ridge board no~ less in depth th~n the <br />cut end of the rafter is required. It shall <br />be a vertical load b~aring member when roof <br />slope is less than 3" in 12", OUBC 2518 <br />19. Rafter ties spaced nmx. 4' o.c. are re- <br />~Hred inmediately above ceiling joists which <br />ere not parallel to ~he rafters. OL~C 2518 Ch)-4 <br /> <br /> 20. Roof pum~lins must not be smaller than the <br /> rafters they support. The m~x. span for 2 X 4/ <br /> 2 X 6 roof purlins is 4" × 6". For purlin sup- <br /> ports provide struts, not smaller than 2 X 4 <br /> with an unbraced length not over B' and not <br /> flatter than 45 degrees to the horizontal to <br /> bearing wall or partitions, oLq~C 25!8 ~q~)-5 <br /> ~ All weather exposed ply~apod s~hall be <br /> ~IIOR type and at least C-C grade. <br /> Attention: P~of overhangs. <br /> 22. Provide safe,ced attic vents ~rith a net <br /> f~ee area of 1/150 of the attic area (or 1/300 <br /> if half is along eaves and the balance at <br /> least 3' higher). OL~3C 3205-c <br />eysRoof shall be sloped for drainage. Vel- <br />shall be supported (flat valleys prohib- <br />ited. ) Shingles (any kind) shall not be <br />stalled on a slope of less than 4" in 12". Com- <br />position shingles require a 15 ~und asphalt <br />felt base sheet. Chapter 32. <br /> <br />~. Provide min, one hour fire separation be- <br />tween garage and house, Separation shall ex- <br />tend to roof line or across ceiling and re- <br />maining bearing ~lls. Use rain. 1 3/8" solid <br />core door. OUBC 503(d) exception A. <br /> <br />25. Enclosed usable space under stairs shall <br />be provided with one hour protection on the <br />enclosed side. OI~BC 3305-(m) <br />26. Elements of appliances which create a <br />glow, spark of flame shall be located a min. <br />of 18" above garage floor, OL%~!C 508 <br />27. Appliances s~bject to mechanical damage <br />shall be guarded by a protective barrier. <br />OUBC 5O8 <br /> <br />28. Clothes dryer located J~n an area that is <br />habitable or containing other fuel b~rning ap- <br />pliances shall be e~xhausted to the outside. <br />OUMC 1903 <br />29. Vent kitchen fm~ to outside via metal <br />ducts. <br /> <br /> <br />