Marion County <br /> <br /> OREGON <br />COMMUNITY DEVELOPMENT <br />DEPARTMENT <br /> <br />t~R~CTOR <br />Craig O. Luedeman <br /> <br />BUILDING INSPECTION <br />(503) 588-5147 <br /> <br />PI.ANNING & <br /> <br />(503) 588-5038 <br /> <br />BOARD OF <br />COMMI$S~ONI~RS <br />Randall frarlke <br /> <br />Mary Pearmine <br /> <br />A D~VIINISTRATIVE <br />OFFICER <br />Ken R~udybush <br /> <br />FIRE SPRINKLER PLANS REVIEW <br /> <br />DATE: <br /> <br />SUBJECT: <br /> <br />SITE #: <br /> <br />OWNER: <br /> <br />TYPE OF CONSTRUCTION: <br /> <br />BUILDING CLAss: <br /> <br />February 24, 1993 <br /> <br />9493 Porter Rd. S.E. <br /> <br />93-00028 <br /> <br />Modern Building Systems Inc. <br /> <br />5-N Fully Sprinklered <br /> <br />B-2 <br /> <br />The plans for the above indicated project are acceptable <br />as submitted subject to the following items noted below: <br /> <br />Dry pipe valves and supply pipes shall be in- <br />stalled in a valve room that is lighted and heat- <br />ed. <br /> <br />Dry pipe systems exceeding 750 gallon capacity <br />shall be capable of delivering water to the <br />spectors test on remote end of system within 60 <br />seconds. <br /> <br />Sway brace system as required in NFPA 13 with <br />lateral bracing at a maximum spacing of 40 feet <br />and tops of risers secured utilizing a four-way <br />sway brace. <br /> <br />Senator Building 220 High Street NE Salem, Oregon 97301-,3670 <br /> <br /> <br />