Laserfiche WebLink
>>> "Paul Nees" <Paul.Nees@state.or.us> 02/11/2009 4:56 PM >>> <br /> Is this a double containment day tank under the generator or a separate <br /> tank in the room? <br /> Is the tank fire-rated? <br /> Paul A. Nees <br /> Deputy State Fire Marshal <br /> Office of State Fire Marshal <br /> Oregon State Police <br /> 4760 Portland Rd NE <br /> Salem, OR 97305 <br /> Tel - 503 934-8289 <br /> Cell - 503 559-0419 <br /> Fax - 503 373-1825 <br /> paul.nees@state.or.us <br /> Premier Public Safety Services <br /> >>> "Troy Wheeler" <twheeler@co.marion.or.us> 02/11/2009 3:58 PM >>> <br /> . Paul, <br /> I recieved some information back from the Architect about this <br /> project. <br /> In this generator room he is placing his generator over 620 gallons of <br /> diesel fuel. I believe that the fuel drove him into the H-3 Occupancy <br /> and that from 903.2.4.1 (OSSC or OFC) he is required a sprinkler <br /> system. <br /> In 903.2(0SSC or OFC) Exceptions lets him remove the sprinkler in a <br /> telecommunications for the engine but not for the fuel. <br /> Do you believe the sprinklers are required in this situation? <br /> Thanks, <br /> Troy Wheeler, Plans Examiner <br /> Marion County Building Inspection <br /> Ph: 503-373-4424 <br /> >>> "Paul Nees" <Paul.Nees@state.or.us> 02/10/2009 1:39 PM >>> <br /> I believe it may be due to the amount of fuel in the tank. I gave him <br /> information quit a while back on the maximum amount of fuel permitted <br /> inside a building. <br /> Paul A. Nees <br /> Deputy State Fire Marshal <br /> tbir Office of State Fire Marshal <br /> Oregon State Police <br />