EX4991 March 2,2007 <br /> 06NK23629 <br /> 3. Test Data, Observations and Results <br /> The tests were conducted at Underwriters Laboratories Inc.in Northbrook, IL. For each <br /> test,details on visual test observations,damage assessment, water demand and sprinkler <br /> operation sequence are presented. <br /> 3.1 Ignition Between Four— 40 ft High Storage with 48 ft Nigh Ceiling <br /> Test I was conducted at approximately 10:00 AM on Friday,October 13,2006. The <br /> initial temperature inside the test room was 70°F. The outdoor temperature was 37°F, <br /> 59%RH and winds were out of west at 19 mph. A summary of the test results is <br /> presented in Table 1. <br /> 3.1.1. Test Observations <br /> After ignition, the fire took about 35 seconds to reach the longitudinal flue. Once fire <br /> reached the top of second tier of boxes,it quickly spread to the ceiling. Visible flames <br /> along the ceiling extended 15 ft. outward in the oast, west and south directions. Radiant <br /> heat from the main array ignited the face of the north target array at approximately 145 <br /> seconds. <br /> Table 3.Test I Visual Observation <br /> Time(seconds) Visual Observations <br /> 441.1 0 Ignition <br /> 42 Flames reach top of 2nd tier <br /> 48 Flames reach top of 3rd tier <br /> 51 Flames reach top of 4th tier <br /> 54 Flames reach top of 5th tier <br /> 57 Flames reach top of 6th tier <br /> 59 Flames reach top of 7th tier <br /> 60 Flames reach top of 8th tier <br /> 64 Flames impinging on ceiling <br /> 89 First sprinkler activation <br /> 145 Face of north target ignites <br /> 3.1.2. Damage Assessment <br /> Damage to the main array was observed Mier fire suppression activity had ended. The <br /> center two bays of the main array were completely involved in the fire as seen in Figure <br /> 11. As noted in Section 3.1.1,the north target array ignited(see Figure 12). There was <br /> some evidence of burn through the north target array at the top two tiers. <br /> 11 <br />