Laserfiche WebLink
FOUND~TzON <br /> <br />1. Footings shall hear on firm undisturbed <br />soil. <br /> <br />2. Fills to be used to support footings <br />shall be engineered (report required) or <br />shall be concrete. OUBC 2903-a <br /> <br />3. Foundation sections 12"/15"/18" wide, <br />6"/7"/8" thick and 12"/18"/24" depth below <br />natural grade and finish grade are required. <br />OUBC Table 29-a <br /> <br />4. Maximum slopes for unstabilized cuts and <br />fills are 2 horizontal to 1 vertical. <br />OUBC 2903-(a) <br /> <br />~ Provide underfloor vents of 1 sq. ft. per <br />150 sq. ft. of underfloor area. Openings <br />shall be as close to corners as practical and <br />provide cross ventilation. <br /> OUBC 2516(o)-6 <br /> <br /> 6. Provide underfloor drainage of space is <br /> subject to ~otential storm or groundwater <br /> accumulation. OUBC 2910 <br /> <br />7. Provide reinforcement for concrete <br />walls over 4' in height, min. #4 bar <br />spaced: horiz, c.c. <br /> vert. c.c. <br />Bars shall be continuous with overlap of <br />min. 10 diameters. One bar 4" from bottom <br />and one 4" from top of fo~-~dation wall. <br /> <br />8. Extend ~" sill bolts, min. 7" into con- <br />crete. Space max. 6' c.c. and within 12" of <br />ends. <br /> <br />9. Provide min. 15" x 24" access to crawl <br />space, located not over 20' from plum~ing <br />cleanouts (OUPC 406-g) or furnace (OUMC <br />804-b). Pipes, ducts and other nonstructural <br />construction shall not interfere with ac- <br />cessability to or within the crawl space. <br />OUBC 2517(c)2 <br /> <br />10. Vapor barriers shall be installed on the <br />fround in crawl spaces and on the warm side <br />of exterior walls. OUBC 5303 (f) 1.d. <br /> <br />o The required clearance for wood members <br /> ve grade is 6" for mudsills, 12" for <br />~irders and 18" for joists. OUBC 2517-c <br /> <br />12. Ail posts to be mounted on approved <br />~u~gr~.s~ OUBC 2517 (c) 4 <br /> <br />CONSTRUCTION REQUIREMENTS <br /> <br />~. Cross bridge or solid block 2" floor <br />joists over 12" in depth every 18' and solid <br />block at supports. <br /> <br />14. Fire block studwalls and partitions <br />(including furred spaces) at floor, ceiling, <br />soffit and at mid height and along stair <br />stringers. Draft stops shall be provided in <br />the following locations. (1) in the concealed <br />space of a floor ceiling assembly in a single <br />family dwelling dividing the area in to ~qual <br />spaces not over 1000 sq. ft. <br />(2) Draft stops shall be installed in the <br />attics, mansards, overhangs and similar con- <br />cealed spaces of buildings containing more than <br />one dwelling unit. Such draft stops shall be <br />above and in line with walls separating <br />tenant s~aces from each other. OUBC 2516 <br /> <br />15. Garage door header shall be min. <br />D.F. #2 with double cripples. <br /> <br />16. Use header, beam or rafter sizes noted <br />On the plans. <br /> <br />Trusses shall be en~inee~ approved. <br /> <br /> 18. A ridge board not less in depth than the <br /> cut end of the rafter is required. It shall <br /> be a vertical load bearing member when roof <br /> slope is less than 3" in 12". OUBC 2518 (h)-3 <br /> <br /> 19. Rafter ties spaced max. 4' c.c. are re- <br /> quired immediately above ceiling joists which <br /> are no~ parallel to the rafters. OUBC 2518 (h.).-4__ <br /> <br /> 20. Roof purlins must not be smaller than the <br /> rafters they support. The max. span for 2 x 4/ <br /> £ x 6 roof purlins is 4' & 6'. For purlin sup- <br /> ports provide struts, not smaller than ~ ~ 4 <br /> with an unbraced length not over 8' and not <br /> flatter than 45 degrees to the horizontal to <br /> bearin~ wall or partitions. OURC 2518 <br /> <br /> 21. Ail weather exposed plywood shall be <br /> EXTERIOR type and at least C-C grade. <br /> Attention: Roof overhanfS.~ .... <br />reProvide screened attic vents with a net <br /> e area of t/150 of the attic area (or 1/300 <br /> if half is along eaves and the balance at <br /> least 3' hi~her).' p_UBC 3205-c <br /> 23. Roof shall be sloped for drainage. Valleys <br /> shall be supported (flat valleys prohibited.) <br /> Shingles (any kind) shall not be installed on a <br /> slope of less than 4" in 1~". Composition shingles <br /> require a 15 pound asphalt felt base sheet. <br /> Chapt~ 32. <br /> <br />24. Provide min. one hour fire separation be- <br />tween garage and house. Separation shall ex- <br />tend to roof line or across ceiling and re- <br />maining bearing walls. Use min. 1 3/8" solid <br />core door. OUBC 503 (d) exce~.gn 4. <br /> <br /> under stairs shall <br /> Enclosed.usable <br /> space <br /> provided w=th one hour protection on the <br />enclosedside. OUBC <br /> <br />26. ~lements of appliances which create a glow, <br />spark of flame shall be located a min. of 1~" <br />above garage floor. OUMC 508 <br /> <br />27. Appliances subject to mechanical damage <br />shall be guarded bg a protective barrier. <br />OUBC 508 <br /> <br /> 28. Clothes dryer located in an area that is <br /> habitable or containing other fuel burning <br /> pliances shall be exhausted to the outside. <br /> OUMC 1903 <br />uCt kitchen outside via metal <br /> Vent <br /> fan <br /> to <br /> <br /> ~ In bathrooms, water closet compartments, <br /> laundry rooms and similar rooms, a mechanical <br /> ventilation system connected directly to the <br /> outside, capable of five air changes per hour <br /> shall be provided where there are no openable <br /> windows. OUBC 1205-a <br /> <br />Provide all habitable with outside <br /> rooms <br /> windows with net areas of not less than 1/!0 <br /> of floor areas nor i0 sq. ft. Every sleeping <br /> room shall have an exterior door or not less <br /> than 5.7 sq. ft. of openable window. The min. <br /> net clear opening height shall be 24 inches. <br /> The min. net clear opening width shall be 20 <br /> inches. The finished sill height shall be not <br /> more than 44 inches. OU~C 1~04 and 1205(a) <br /> <br />32. Windows between the carport and the dwel- <br />ling shall not be openable. OUBC 1214 <br /> <br />33. Provide at least one 36" swinging {exit) <br />door. OUBC 3303(e) <br /> <br /> <br />