Laserfiche WebLink
3.5 <br />3.6 <br />3.7 <br />3.8 <br />EXHAUST FAN TESTING <br />A. Location <br />B. Manufacturer. <br />C. Model. <br />D. Air flow, specified and actual. <br />E. Total extemal static pressure, spec~ed and actual. <br />F. Inlet pressure. <br />G. Discharge pressure. <br />H. Fan RPM. <br />RETURN AIR/OUTSIDE AIR TESTING <br />A. I dentification/location. <br />B. Design air flow. <br />C. Actual air flow. <br />D. Design return air flow. <br />E. Actual retum air flow. <br />F. Design outside air flow. <br />G. Actual outside air flow. <br />H. Return air temperature. <br />I. Outside air temperature. <br />J. Required mixed air temperature. <br />K. Actual mixed air temperature. <br />L. Design outside/retum air ratio. <br />M. Actual outside/return air ratio. <br />ELECTRIC MOTORS TESTING <br />A. Manufacturer. <br />B. HP/BHP. <br />C. Phase, voftage, amperage; nameplate, actual, no load <br />phases of 3-phase motors. <br />D. RPM. <br />E. Service factor. <br />F. Starter size, rating, heater elements. <br />V-BELT DRIVES TESTING <br />A. I dentification/location . <br />B. Required driven RPM. <br />C. Driven sheave, diameter and RPM. <br />D. Belt, size and quantity. <br />E. Motor sheave, diameter and RPM. <br />Record voltage and amperage on all <br />4 <br />