Laserfiche WebLink
~ ... <br />~~ ~~~\~\~~~~\\ <br />See Note 3. <br />Telco, CAN, PGE '~ <br />! - - , <br />Pedestal Area 2,~ ., ;,~,K~x~:., <br />I 2~ See Note 4. <br />Suggested barrier post locations ---- ~ 4' 4~ ~~- Suggested barrier post locations <br />, Front <br />~ ! <br />'~~~ X X• <br />~ <br />i <br />This area to be \ <br />kept ciear <br />. <br />~- y -- <br />n <br />e <br />~-y <br />~y. <br />~-$ <br />, ~ ~ ~ <br />Frcnt View with Doors Closed <br />(See Note 2.) <br />MINIMUM DISTANCE REQUIRED <br />X= 10' clear area in front of unit to allow use of hot sticks (See Note 2). <br />Y= 8' if structure is of combustible material. <br />Y' = 2' to non-combustibie building surfaces having no openings closer than 8'. <br />NOTES <br />1. Consult OREGON ADMINISTRATIVE RULES 918-290-110 and local building codes for more <br />customer information. <br />2. Front of pad-mounted transfo~mer to be located away from building walls or other barriers to <br />allow for safe working practices. If front of transformer must face wall, allow "X" dimension for <br />working area instead of "Y"' dimension. <br />3. Maintain 4 Ft. clearance around side and 2 Ft. clearance on back of unit from all other uses <br />(i.e., telco, cableN, water, shrubbery, etc.). Maintain 10 Ft. clearance in front of units for work <br />area. <br />4. See STD. LC-257-50-01 for use of steel barriers to protect transformers from traffic. <br />PGE PROPRIETPRY MATERIAL - THIS INFO IS BASED ON ASSUMPTIONS 3 CRRERIA NMICH MAY NOT BE VALID OUTSIOE THE PGE ELECTRIC SYSTEM - FOR INTERNAL USE ONLY <br />PAD-MOUNTED TRANSFORMER CLEARANCES DESIGN X CONSTRUCTION <br />T & D STANDARDS <br />PAD-MOUNTED TRANSFORMERS DATE 1-1-96 <br />P.G.E. CO. STANDARD LC-257-10-01 <br />