,:~: . . <br />Jeff Moore <br />Courthouse Square <br />Project No. 9828 <br />March 23, 1999 <br />Page 2 of 3 <br />6. A change will be processed to require 60-minute fire ratings on Doors 1209A and <br />1239B. We note that the masonry partition enclosing these rooms extends to the <br />strudural concrete slab above. <br />7. With respect to standpipe connedions, please refer to mechanical drawings. <br />Proposal Request No. 003 indicates additional standpipe connections as you <br />require. <br />8. With resped to Door 1257A, w~e poopose modifying the pian as per Drawing SD-002 <br />(attache~. <br />9. The spedfications and drawings requir~e that the elevator shafts be 2-hou~ fire ~ated <br />and that the doors be 90-minute fire rated. Can this issue be cleared with the <br />elevator submittal drawings? <br />10. The "a+oss corridor double egress doors" are designed to provide smoke controi at <br />the elevator lobbies. <br />Second Floor. <br />1. Standpipes are tocated in fumed-out locations adjacerrt to stairvvell doors with <br />~- - - . ._ .. <br />"` connedions extending into the stairwell of each floor as per mechanical drawings. <br />2. A letter requesting oonsideration of 60-minute fire rated giass~ proteded by deluge <br />type sp~inkier protedion to both sides, has been seM to Nathan Brovm. <br />:. 3. Rega~cling exlting from Room 2276. please note the proposed plan revision shown <br />on Drawing SD-008. The CouMy's Tax Office has been absorbed with the <br />Assesso~'s DepartmeM. <br />_ .~ <br />General CommeMs: . <br />1. Standpipe system design is incaporated in mechanical drawings. Pe~tc.81K811y tias <br />arrived at an aa~ommodation which permits defemed submi~ai of sprinkler drawings <br />and fire alarm drawings, both of which are cumently in produdion. <br />2. Fire rating of Doors 1151A and 1152A to be accommodated by change orcier. <br />Piease review requirements for 1253B, 1234A, and P198A. <br />3. See above item regarding 1209A and 1239B. <br />4. Addendum No. 3 changed Doors 1121 B,1121 C,1221A,1221 B, 1240A, 12408, and <br />1131A to 90-minute fire rating. <br />5. Addendum No. 1 equipped Doors 1221A, 1221B, 4211A, and 4211B with panic <br />hardware. A change will be issued to require the same on 1175D. <br />u <br />