Laserfiche WebLink
OO 1997 Portiand General Electric. All rights reserved <br />. The vault door shali have a PGE keyway, which accepts the standard PGE station key. <br />If any other locked doors must be passed through to get access to the vault, then the <br />customer should provide lock boxes. <br />Duct Sizing <br />Ducts to be used for installation of electrical conduits should meet the following standards. <br />Primary Raceway <br />Ducts intended for primary conductors should be electrically outside of the building. <br />This is accomplished by following the NEC section 230-6. Conductors shall be <br />considered outside of a building or other structure under any of the following conditions: <br />(1) where installed under not less than 2 inches of concrete beneath a building or other <br />st~ucture; (2) where installed within a building or other structure in a raceway that is <br />encased in concrete or brick not less than 2 inches thick; or (3) where installed in a <br />transformer vault conforming to the NEC requirements. Thin-wall IMC ducts and rigid <br />ducts is not acceptable. Ducts from the property line to the building is supplied by the <br />customer and will be Schedule 40 electrical ducts. All bends in the ducts run should be <br />steel, with 36-inch radii minimum. See Ducts & Road Crossings Design Standard, <br />STD. LD-310-10, "Conduit Sizing Criteria" for determination of duct size. Be sure to <br />increase duct dimensions if runs are over 150 feet and more than one bend. <br />Each duct entering through the vault floor should have a 4- to 6-inch concrete lip <br />poured around it to keep water or oil from entering the duct. <br />For duct runs lon~er than 150 feet, duct diameter is to be increased by 1/2 inch; for <br />~ three 90 degree bends per run, duct diameter is to be increased an addition 1/2 inch. <br />Consult with the Engineer or Design's supervisor when run exceeds 300 feet in total <br />length or exceeds 270 degrees in bends. See Ducts & Road Crossings Design <br />Standard, STD. LD-310-10, "Jamming Ration Calculations". <br />Secondary Raceway <br />Secondary ducts should be sized according to The Oregon Electric Service <br />Requirements book. (See Table 2 and Table 3) A rule of thumb to follow is to allow <br />one 4-inch duct for each 400 amps of service. It is preferred that 4-inch ducts be used <br />in all cases. <br />Bends in secondary ducts shall be steel or fiberglass and have a minimum radius of 36 <br />inches for duct sizes up to 4". <br />Sheet metal gutter ways can be used for the secondary raceway between a dry-type <br />transformer and the distribution panel. The recommended minimum cross-sectional <br />area for a gutter way is 64 square inches. <br />PGE PROPRIETARY MATERIAL - THIS INFO IS BASED ON ASSUMPTIONS 8 CRITERIA WHICH MAY NOT BE VALID OUTSIOE THE PGE ELECTRIC SYSTEM- FOR INTERNAL USE OP~Y <br />UNDERGROUND BUILDING CLASS A <br />VAU LTS <br />UNDERGROUND <br />P.G.E. CO. STANDARD <br />X I DESIGN I I CONSTRUCTION <br />I T8~D STANDARDS ~ <br />DATE 08-09-96 <br />LD-310-07-09 <br />~°~E~`~~ -- Menu - Close - <br />