Laserfiche WebLink
NO CHASE GREASE DUCT <br />INSPECTION POINTS <br />The following installation details should be verified to assure a correctly installed NO <br />CHASET"' GREASE DUCT system: <br />1. The pipe must carry the BOCA/SBCCI Label. <br />2. Cleanout access ports are installed in accordance with NFPA 96-1994, Chapter 4. <br />3. The proper sealant (Metal-Fab P/N P080) must be used to seal the joints. <br />4. Supports must be installed in accordance with the support limitations set forth in the <br />instructions and must be fastened securely to the building structure. <br />5. Cleanout access ports are installed so that the built in grease dams are in the correct <br />orientation. <br />6. Grease drains are at the low points of the duct in the area drained and are connected <br />to acceptable grease receptacles. <br />7. Expansion joints are installed in a location such that longitudinal movement is <br />unrestricted by supports or surrounding structure. <br />8. Fan connections must be properly sealed. The duct to fan joint must be sealed with <br />Metal-Fab P/N P080 sealant or gasketed with gasket material in accordance with <br />NFPA 96-1994. <br />9. Any duct penetration of a rated wall must be firestopped in accordance with the <br />installation instructions. <br />METAL-FAB,N <br />~. <br />F <br />MANUFACTURER OF PRODUCTS <br />FOR ENVIRONMENTAL SVSTEMS <br />P. O. BOX 1138 ~ WICHITA, KANSAS 67201 <br />(316) 943-2351 • FAX (316) 943-2717 <br />800-835-2830 <br />~07998 Metal-Fab, Inc. Litho in U SA. <br />Form No. L1508-12/98 <br />