Laserfiche WebLink
Table 2. Alarm Diagnosis and Troubleshooting Guide <br /> Label Color Indication Potential Causes Corrective Action -. <br /> Surge Dosing Tank Red High Level Inflow Inspect all fixtures in the buildings for leaks,repair as <br /> necessary <br /> Infiltration Identify source(s)and repair or replace as necessary <br /> • Failure of one or more floats Check float function and repair or replace,as necessary <br /> Blue Pump Fail Failure of a pump or related electrical component Diagnose and repair or replace as necessary <br /> Red Low Level Normal tinier setting is too long Check timer setting in relation to float settings and pump <br /> flow rate. Adjust only with input from designer. <br /> Failure of one or more floats Check float function and repair or replace,as necessary <br /> Control system malfunction Seek professional assistance <br /> MicroFAST Tank Blue Blower Fail Thermal overload or current disruption See FAST unit manuals in Appendix or seek <br /> professional assistance <br /> CES-Albany,OR St.Innocent Winery I 0&M Manual <br /> Doc: 2018240028 Stlnnocent Winery OM tables-forms-O&M Table 2 May 2018 <br />