HWHIO8HWOI EC 2/25/20 00213DER2 THE HOT WATER HEATER TEMP IS 102. IT USUALLY RUNS <br /> 120. PLEASE INVESTIGATE IF A HEATER ELEMENT HAS <br /> FAILED.---checked t-stat and control power,checked elements.didn't <br /> find anything wrong seems to be holding temp now <br /> • PNL108H BJL 1/29/20 00127GCP2 SWAP THE STOP&RUN LIGHT MODULES SO THAT RED IS <br /> RUN,GREEN IS STOP.---Swapped pump running and stopped light <br /> modules to follow facility standards. <br /> 111 ST PUMP STATION <br /> ITEM BY C-DATE W/O# <br /> 111 BJL 1/23/20 91209BJL1 THE NORTH AND SOUTH LIGHT FIXTURES ARE NOT <br /> WORKING. LAMPS WHERE REPLACED AND FIXTURES <br /> STILL DON'T WORK. BALLASTS AND/OR PHOTOCELL MAY <br /> NEED REPLACING.---Replaced ballast and capacitors and light <br /> bulbs. <br /> 112 PRI TREATMENT ELECT FACILITY <br /> ITEM BY C-DATE W/O# <br /> ACU112AIR02 RBL 7/7/20 00701 WJMI UNIT DOES NOT SHOW OVERLOAD ON DCS HVAC <br /> SCREEN...Complete <br /> UPSI 1 lB BJL 11/10/20 01106WM01 UPS IS IN ALARM. BATTERY FAILURE OPEN CELL <br /> VOLTAGE.---changed batteries in UPS <br /> 116 EFFLUENT ANALYZER BUILDING <br /> ITEM BY C-DATE W/O# <br /> 116 MJN 6/5/20 90918FJS2 INSTALL LED WALLPACK FIXTURE ON BACKSIDE OF EAB <br /> TO LIGHT UP SFE SAMPLE PUMP AREA AND REPLACE TWO <br /> OLD METAL HALID FIXTURES BY SAMPLERS.---Work <br /> completed by NSE <br /> • 116AIT153E CLC 10/13/20 00629CLC1 REPLACE PERISTAITIC PUMPS IN ANALYZER---all pumps <br /> replaced <br /> 116AIT153E CLC 11/16/20 01109LLG1 FAILURE ALARM ON DCS DISPLAY,ANALYZER DISPLAYS <br /> "LOW LIGHT"AND THEN RETURNS TO NORMAL---cleaned <br /> gas flow cell <br /> ELTI 16B MJN 3/5/20 00218BJL1 EMERGENCY LIGHT FAILED 30 MINUTE TEST.NEW <br /> 1.2V/1200 mAH BATTERY IS ON ORDER.---Replaced battery <br /> PMPI I6HYPO03 CLC 11/16/20 01109KJW1 PUMP IS NOT DISCHRGING HYPO---replaced pump <br /> SMPI 16CFE01 PJS 3/3/20 00303DER2 THE CFE SAMPLER HAS A HOLE IN THE PINCH HOSE. HOSE <br /> NEEDS TO BE REPLACED. Replaced hose. <br /> SMP116CFE01 CLC 7/1/20 00624CLCI PROVIDE VENTILATION TO SAMPLER ENCLOSURE---vents <br /> installed <br /> SMPI 16CFE01 RBL 8/5/20 00803LLG4 FRIDGE IS NOT ACHIEVING TEMPERATURE <br /> SETPOINT...Defrosted evaporator. <br /> SMPI 16CFE01 CLC 11/18/20 01117DER2 PINCH HOSE IS LEAKING---replaced hose <br /> SMP116NFE01 RBL 7/22/20 00721JLCI Sampler refrigerator temp is at 6 deg c.Temp controller is showing 7 <br /> • deg c. Maybe bad refrigerator?...Defrosted refrigerator. <br /> SMP116NFE01 RBL 8/5/20 00803LLG3 FRIDGE IS NOT ACHIEVING TEMPERATURE <br /> SETPOINT...Defrosted evaporator. <br /> Page 19 of 20 <br />