"T''Of ELECTRICAL MAINTENANCE LOG <br /> AT 7rAJR SFAV1(t <br /> JANUARY 1,2020 THROUGH DECEMBER 31, 2020 <br /> • <br /> ITEM BY C-DATE W/O# <br /> 012FIT630A PJS 8/3/20 00803PJS1 TOTALIZER FUNCTION NOT WORKING.Totalizer"A"now <br /> functioning. Since the Flow is in GPM, I changed the totalizer unit <br /> from Mgal to gal as well. <br /> 012FIT631A PJS 8/3/20 00803PJS2 TOTALIZER FUNCTION NOT WORKING.Totalizer"A"now <br /> functioning. Since the Flow is in GPM, I changed the totalizer unit <br /> from Mgal to gal as well. <br /> 001 GENERAL IN-PLANT <br /> ITEM BY C-DATE W/O# <br /> 001 MJN 2/10/20 80501BDW1 INSTALL AND REWIRE, INCLUDING ADDING CONDUIT,FOR <br /> NEW THERMOSTATS PER ENERGY TEAM <br /> EVALUATION...Work completed by NSE <br /> 001 MJN 5/6/20 90405MJN2 AT SOUTH END OF CCC BASIN.CHINA HAT LIGHT POLE <br /> DOES NOT WORK. REMOVE LAMP AND BALLAST. INSTALL <br /> DIRECT WIRED LED LAMP.---work completed by NSE <br /> 001 MJN 6/8/20 CIPDCS001 INSTALLATION OF COMMON DCS I/O AND <br /> COMMUNICATIONS HARDWARE, INCLUDING CONDUITS <br /> AND ENCLOSURES,TO TIE PLANT I/O UPGRADE <br /> PROCESSES TOGETHER...Work completed by NSE <br /> 001FITIOIA CLC 4/29/20 91019DER1 FLOW METER IS SHOWING "INPUT BAD"ON DCS.---powered <br /> down instrument and pulled/reseated electronics,no problem since. <br /> • configured spare electronics in store room <br /> 001 FIT 101 A CLC 10/13/20 00817LLG2 DISPLAY IS WASHED OUT---eplaced display from spare meter, <br /> ordered new display,reset totalizer to 33.14 mgd,rtplaced electronics <br /> after analog output failure. <br /> 001TE299A PJS 11/24/20 01123PJS1 WEATHERTOWER TEMPERATURE AND HUMIDITY <br /> ELEMENTS'SUN SHIELDS ARE BEING BENT DOWN BY <br /> PERCHING BIRDS. Bird spike strips were installed on top of sun <br /> shields. <br /> GATOOIVEH03A MJN 2/24/20 00217JCF1 THE GATE WON'T OPEN WITH ANY INPUT. KEYPAD,CARD <br /> READER OR PUSHBUTTON ON GATE PANEL.---Open bumper <br /> transmitter was draining battery's. Metro came out and replaced <br /> tranmitter.working ok now. <br /> GATOOIVEHO3A BJL 6/16/20 00615BDW I GATE OPERATOR IS NOT WORKING.---Replaced batteries in <br /> entry gate north bump switch. <br /> GATOOIVEH03A BJL 7/7/20 00706GCP1 THE GATE WILL NOT OPEN WITH CARD NOT THE KEY <br /> PAD.---Replaced dead batteries in north bump switch. <br /> IC-10 MJN 10/26/20 00915BDW1 REPLACE 32 YEAR OLD DETERIORATED IC VAULT.----Work <br /> completed by NSE <br /> PSCOO1A MJN 8/31/20 00824EC01 DIRT IS BUILT UP TO TOP OF CONDUITS IN TERMINATION <br /> COMPARTMENT AND NEEDS TO BE PULLED BACK.---Pulled <br /> gravel and dirt back so it would not fall into conduits. <br /> PSC002B MJN 1/21/20 90915EC01 PROTECTIVE CAPS NEED TO BE INSTALLED ON WAY 3 <br /> SNOW THAT THE 2400V UNOX TRANSFORMER HAS BEEN <br /> REMOVED.---protective caps installed. <br /> PSC003A MJN 8/31/20 00824ECO2 DIRT IS BUILT UP TO TOP OF CONDUITS IN TERMINATION <br /> COMPARTMENT AND NEEDS TO BE PULLED BACK.---Pulled <br /> gravel and dirt back so it would not fall into conduits. <br /> Page 1 of 20 <br />