Laserfiche WebLink
PSC041A MJN 8/31/20 00824EC03 DIRT IS BUILT UP TO TOP OF CONDUITS IN TERMINATION <br /> COMPARTMENT AND NEEDS TO BE PULLED BACK.---Pulled <br /> gravel and dirt back so it would not fall into conduits. <br /> PSC042B MJN 8/31/20 00824EC04 DIRT IS BUILT UP TO TOP OF CONDUITS IN TERMINATION <br /> COMPARTMENT AND NEEDS TO BE PULLED BACK.---Pulled <br /> gravel and dirt back so it would not fall into conduits. <br /> 002 WELL#2 • <br /> ITEM BY C-DATE W/O# <br /> 002FCV100A MJN 4/27/20 00424JES1 THE VALVE IS STUCK CLOSED AND IT ISN'T SHOWING <br /> OPEN OR CLOSED ON THE DCS.---The valve was okay but <br /> found the breaker off that supplies power to the load center at#2 well. <br /> Turned the breaker back on,tested the valve and adjusted the limit <br /> switch on the valve. <br /> 004 SOUTH DIGESTER FACILITY <br /> ITEM BY C-DATE W/O# <br /> 004 BJL 7/27/20 00720BDW1 REPLACE EXPIRED SELF ILLUMINATING EXIT SIGN AS PER <br /> KEIZER FIRE DEPARTMENT.---Replaced expired self illuminating <br /> exit sign <br /> 004 MJN 8/1/20 00716BDW6 KEIZER FIRE DISTRICT INSPECTIONS REVEALED THE <br /> FOLLOWING VIOLATION. 1006.1 ILLUMINATION REQUIRED: <br /> REPLACE EXPIRED EXIT SIGN ON NORTH WALL OF SOUTH <br /> DIGESTOR BASEMENT. <br /> REPLACE OR REPAIR EGRESS LIGHTING IN BASEMENT OF <br /> SOUTH DIGESTOR BUILDING. <br /> Replaced self illuminating exit sign. <br /> Repaired push to test button on egress lighting. • <br /> 004 MJN 10/23/20 30315BDW2 PREPERATION AND INSTALLATION OF NEW DCS RIO <br /> CABINET TO REPLACE RIO-004. INSTALL UPS POWER <br /> SUPPLY PANEL W/UPS FOR CONNECTION TO THE NEW <br /> RIO-004 IN THE SOUTH DIGESTER CONTROLROOM. <br /> INSTALL NEW FIBER FROM SOUTH DIGESTER TO THE <br /> FLOAT THICKENER DCSRIO012A. RE-WIRE EXISTING I/O <br /> INTO NEW CABINET. <br /> FILES: REMOVE TIC-152 AND TIC-153 FROM FILES. RENAME <br /> FILES TE-152 AND TE-153 TO 004TE152A AND 004TE153A <br /> RESPECTIVELY.ADD FILES 004TE152A,004TE153A, <br /> 004TT152A,AND 004TT153A. [PJS] <br /> Closing this work order and reissueing a new work order because it <br /> has been expired by North Coast Electric accounting office. <br /> 004FSL007A EC 4/15/20 00414BNW1 FLOW SWITCH DOES NOT TURN OFF MOTOR ON LOSS OF <br /> SEAL WATER.---Replaced and tested flow switch <br /> 004FSL008A BJL 8/6/20 00803BNW3 COMPRESSOR DOES NOT SHUT OFF WHEN SEAL WATER IS <br /> TURNED OFF---Flow switch worked when tested. <br /> 004FSL010A MJN 5/5/20 00414BNW2 FLOW SWITCH DOES NOT TURN OFF MOTOR ON LOSS OF <br /> SEAL WATER.---Cleaned and tested flow switch.switch is working <br /> electrically. switch required 2 GPM to actuate. flow measurement is <br /> just above 2 GPM. Mechanics replaced some clogged piping and <br /> water pressure went from 20psi ti 50psi and lots of flow now. <br /> Page 2 of 20 <br />