FACP005A MJN 5/5/20 00409MJN1 SYSTEM TROUBLE OF FIRE ALARM PANEL <br /> "COMMUNICATIONS FAIL"---Assisted point monitor with <br /> troubleshooting system trouble on FACP005A.Technition suspected <br /> noise on phone line was the cause of trouble and suggested we <br /> upgrade to wireless communications. <br /> PWH-0501 MJN 5/5/20 00427BNW1 HEATING ELEMENT IS NOT COMING ON. BREAKER WAS • <br /> TRIPPED.---Replaced contactor for heating element. <br /> UH005AIR06 MJN 3/5/20 00210JAM 1 NORTHEAST HEATER FAN MOTOR IS NOISY AND NOT <br /> TURNING WELL, MOTOR OR MOTOR BEARINGS MAY NEED <br /> REPLACED.----Replaced motor and back in service. <br /> UH005AIRO6 BJL 3/20/20 00305MJN1 BELIMO ACTUATOR HAS A BROKEN FITTING AND IS NOT <br /> CLOSING THE VALVE ALL THE WAY.ACTUATOR NEED TO <br /> BE REPLACED.---Replaced flex conduit and actuator. <br /> VEH-0502 JAM 11/10/20 01101KJW1 BATTERIES MAY NOT BE CHARGING.CART IS SLOW AND <br /> SURGES.---Replaced batteries and cables. Set speed and <br /> re-generative braking to maximum. <br /> VEH-0503 EC 3/5/20 00215WJMI FORWARD/REVERSE SWITCH DOES NOT WORK EVERY <br /> TIME. SOMETIMES IT TAKES MANY TRY'S TO <br /> WORK.---Installed new forward/reverse switch. <br /> VEH-0503 JAM 12/3/20 01125WJMI BATTERIES MAY NOT BE CHARGING.---Replaced batteries. <br /> VEH-0505 BJL 3/25/20 00312JAM2 FORWARD/REVERSE SWITCH DOES NOT WORK EVERY <br /> TIME. SOMETIMES IT TAKES MANY TRY'S TO <br /> WORK.---Replaced switch. <br /> VEH-0903 MJN 2/26/20 90814BNW1 PLUG INTERLOCK DOES NOT WORK.CHARGING CORD <br /> CONNECTION DOES NOT DIABLE TRAVEL WHEN PLUGGED <br /> INTO POWER AND IT USE TO.---problem could not be duplecated. <br /> VEH-0904 EC 2/28/20 00218JAKI HEAD LIGHTS DON'T COME ON BUT TAIL LIGHTS • <br /> DO.---found a broken ground wire.repaired wire and replaced <br /> headlamps. <br /> VEH-11504 JAM 10/27/20 01023JMG1 INSTALL DOME LIGHTS INSIDE THE CAB.---Done. <br /> VFD005EXHOI EC 9/3/20 00813ECO2 INSTALL A POWER DISTRIBUTION BLOCK BETWEEN LOAD <br /> REATOR AND MOTOR TO PREVENT DAMAGE TO LOAD <br /> REACTOR SCREWS WHEN MEGGING MOTOR.---Installed <br /> power distribution block and extended wires. <br /> VFD005EXH02 EC 9/3/20 00813EC03 INSTALL A POWER DISTRIBUTION BLOCK BETWEEN LOAD <br /> REATOR AND MOTOR TO PREVENT DAMAGE TO LOAD <br /> REACTOR SCREWS WHEN MEGGING MOTOR.---Installed <br /> power distribution block and extended wires. <br /> 007 WOOD SHOP/WAREHOUSE <br /> ITEM BY C-DATE W/O# <br /> 007 MJN 8/1/20 00716BDW2 KEIZER FIRE DISTRICT INSPECTIONS REVEALED THE <br /> FOLLOWING VIOLATION. 605.1 ABATEMENT OF <br /> ELECTRICAL HAZARDS: REPAIR WIRING IN CONEX BOX <br /> EAST OF WOODSHOP. <br /> Unauthorized power wiring has been removed from contractor <br /> owened conex. <br /> • <br /> Page 6 of 20 <br />