Laserfiche WebLink
007 MJN 8/1/20 00716BDW4 KEIZER FIRE DISTRICT INSPECTIONS REVEALED THE <br /> FOLLOWING VIOLATION.605.5 EXTENSION CORDS: <br /> DISCONTINUE USE OF EXTENSION CORDS THAT IS <br /> CONNECTED INTO CONEX BOX WITH MULTI PLUG <br /> ADAPTOR OR AND EXTENSION CORD PLUGGED INTO IT. <br /> • unauthorized power wiring has been removed from contractor owned <br /> conex <br /> 010 N DIGESTER COMPLEX <br /> ITEM BY C-DATE W/O# <br /> 010 EC 1/16/20 91202EC01 REPLACE ALL T8 LAMPS IN BUILDING WITH BYPASS THE <br /> BALLAST LED REPLACEMENT LAMPS.---rewired and relamped <br /> light fixtures with LED lamps <br /> 010 EC 4/9/20 00402DJHI THE LIGHT ABOVE THE OVERFLOW BOX ON NPD#1 IS <br /> OUT.---Replaced lamp and tested photocell <br /> 010 EC 7/24/20 00723MJN1 PHOTO CELL SEEMS TO HAVE FAILED. LIGHT IS ON ALL <br /> THE TIME.---Replaced and tested photcell <br /> 010 MJN 6/8/20 CIPRIO010 INSTALLATION OF NEW DCS RIO CABINET IN THE NORTH <br /> DIGESTER FACILITY. INCORPORATE FIBER FROM THE <br /> FLOT THICKENER TO THE NORTH DIGESTER <br /> FACILITY...Work completed by NSE <br /> 010 MJN 11/16/20 60301BDW2 INSTALLATION OF NEW DCS RIO CABINET IN THEN DIG <br /> BLDG. CREATE A FIBER PATH FROM N DIG TO FLOT...Work <br /> completed by NSE <br /> AI-1002 PJS 12/24/20 01116PJSl FYRITE IS LOW ON FLUID.ALSO FIND AUTHORIZED <br /> SUPPLIER OF FYRITE SPARE PARTS. Filled[RBL]. Fyrite 60% <br /> CO2 is now obsolete according to Bacharach HQ. Looking for <br /> II/ substitute instrument since parts other than the fluid are not available. <br /> [PJS]. <br /> LI-114 PJS 9/23/20 00919SRA1 INDICATOR IS READING INCONSISTENTLY.VALUE FOR <br /> LEVEL CHANGES FOR NO REASON. Purged bubbler. 138" <br /> before, 142"after. <br /> TT-121 PJS 7/30/20 00728DER1 NPD#1 TEMP. PROBE HAS NOT MOVED FROM 100.0 DEG F <br /> FOR 2 DAYS.THE HOT WATER VALVE ON THE HEAT <br /> EXCHANGER IS CLOSED.Transmitter would lock-up it's output, <br /> even if probe wires were removed.Only way to reset was to cycle <br /> power on transmitter. Replaced INOR IPAQ-Hplus transmitter, <br /> configured,calibrated,and ordered another spare. <br /> VFDOIODS01 EC 3/10/20 00306EC01 COOLING FAN#3 NEEDS REPLACING. BEARINGS ARE VERY <br /> NOISY---Replaced cooling fan <br /> 011 CENTRIFUGE <br /> ITEM BY C-DATE W/O# <br /> 011 EC 6/5/20 00511GCP3 RUN CONDUIT AND WIRE UP CONVEYOR#3 AFTER <br /> MECHANICS REINSTALL CONVEYOR.----Completed <br /> 011 EC 6/5/20 00527MJN 1 INSTALL A MOTOR RATED MANUAL STARTER ON <br /> CONVEYOR#3 SO TRUCK DRIVERS CAN TURN OFF <br /> CONVEYOR WHILE SWAPPING TRUCKS---Installed new <br /> disconnect switch and tested. <br /> 011 MJN 8/25/20 00819GCP4 PROVIDE TEMPORARY FEED FROM GRINDER POWER TO <br /> • TEMPORARY MUFFIN MONSTER WHILE CENTRIFUGE <br /> GRINDER IS BEING REPAIRED.---Wired in temporary grinder and <br /> installed correct motor protection circuit breaker <br /> Page 7 of 20 <br />