Laserfiche WebLink
945 Olney, Aumsville <br />December 22, 1992 <br />Page 2 <br /> <br />guardrails shall have intermediate rails or an ornamental pattern such <br />that an object 12 inch diameter cannot pass through where a stairway is <br />not accessible to the public.). (lTl1) Rail spacing complying with OSHA <br />standards are an acceptable alternate. <br /> <br />A water supply sufficient to control a potential fire is required. <br />Appendix III-A of the Uniform Fire Code. Contact the local fire <br />department for requirements. The chief shall establish the minimum <br />residual pressure and flow duration when determining fi~e flow. <br /> <br />Portable fire extinguishers shall be provided and installed as required <br />by applicable standards and as directed by the authority having <br />jurisdiction. (U.F.C. 10.303; U.F.C. std. NO. 10~1) <br /> <br />The plans for the required automatic sprinkler system are to be <br />submitted to Marion County Building Inspection for plan review and <br />approval prior to installation. <br /> <br />The exterior building envelope, heating, ventilating, air conditioning <br />and service water heating systems shall comply with Chapter 53, Energy <br />Conservation. Submit certification of conformance by an Oregon <br />registered architect or engineer. ($301(c)) <br /> <br />Suspended ceiling systems shall be braced for lateral loads. Where <br />substantiating design calculations are not provided, horizontal <br />restraints shall be effected by four NO. 12 gage wires secured to the <br />main runner within 2 inches of the cross runner intersection and splayed <br />90 degrees from each other at an angle not exceeding 45 degrees from the <br />plane of the ceiling. A st~ut fastened to the main runner shall be <br />extended to and fastened to the structural members supporting the roof <br />or floor above. The strut shall be adequate to resist the vertical <br />component induced by the tracing wires. These horizontal restraint <br />points shall be placed 12 feet on center in both directions with the <br />first point within 6 feet from each wall. Attachment of the restraint <br />wires to the structure above shall be adequate for the load imposed. <br />(UBC Std. 47-18 Sec. 47.1812(c)) <br /> <br />only "intermediate" and "heavy duty" ceiling systems may be used for the <br />support of lighting fixtures. Ail lighting fixtures shall be positively <br />attached to the suspended ceiling system. The attachment device shall <br />have a capacity of 100 percen~ of the lighting fixture weight acting in <br />any direction. When "intermediate" systems are used, NO. 12 gage <br />hangers shall be attached to the grid members within 3 inches of each <br />corner of each fixture. Tandem fixtures may utilize come, on wires. <br />Where "heavy duty" systems are used, supplemental hangers are not <br />required if a 48-inch modular hanger pattern is followed. When cross <br />runners are used without supplemental hangers to support lighting <br />fixtures, these cross runners must provide the same carrying capacity as <br />the main runner. Lighting fixtures weighing less than 56 pounds shall <br />have, in addition to the requirements outlined above, two No. 12 gage <br />hangers connected from the fiature housing to the structure above. <br />These wires may be slack. Lighting fixtures weighing 56 pounds or more <br />shall be supported directly from the structure above by approved <br />hangers. (UBC Std. 47-18 Sec. 47.1813) <br /> <br /> <br />