Laserfiche WebLink
Robert~ <br />October 28, 1992 <br />Page 2 <br /> <br />There is a framed wall hanging from the 3x4 beams 12" off the ground. This <br />needs to be addressed in the engineering calculations. <br /> <br />One item not mentioned in our conversation was lateral wall bracing. <br />have the engineer submit calculations for this also. <br /> <br />We need to be notified of the removal of the carport or engineering calcula- <br />tions and details submitted to Marion County for review on or before November <br />27, 1992 to avoid legal action. <br /> <br />In regard to the new roof on the sewing room addition. Submit a section view <br />of the new roof framing showing 2x4 rafters at 16" o.c. with 3/8" tempered <br />glass and application and fees to Marion county on or before November 6, 1992 <br />to avoid legal action. <br /> <br />We will not require a permit for the sewing room addition at this time with <br />the information we now have as you have stated that it is pre-existing. If at <br />such time it is documented that the sewing room addition was not pre-existing, <br />we do reserve the right to reconsider that decision. <br /> <br />If we may be of any further assistance in this matter, please feel free to <br />call. We would like to get this issue resolved as soon as possible as you <br />were originally notified of this problem on September 18, 1992. <br /> <br />sincerely, <br /> <br />SANDRA FREILINGER <br />PLANS EXAMINER <br /> <br />DONALD WOODLEY <br />BUILDING OFFICIAL <br /> <br />CC: <br /> <br />file <br />Bert Stone, Chief Inspector <br />Jerry 8., Structural Inspector <br /> <br /> <br />