Laserfiche WebLink
TFP370 <br /> Page 10 of 12 <br /> III Components <br /> 1 - Frame 4 - Bulb *Temperature rating is <br /> 2 • Button 5- Deflector* indicated on deflector. <br /> 3 - Seating 6 - Compression <br /> Assembly Screw <br /> 6 _ /. } ... • <br /> NIL, -"t fi <br /> 5* <br /> 3 (12,7 mm) 2-3/8- <br /> NOMINAL a (60,3 mm) <br /> 2 c MAKE-IN <br /> 2 <br /> � _ . _ ..�_ <br /> 1 WRENCH 3/4' <br /> CROSS FLAT NPT <br /> SECTION UPRIGHT <br /> FIGURE 4 <br /> ULTRA K17,286°F(141°C), UPRIGHT(TY7IOS)SPRINKLERS <br /> Switch Setting Low Air Threshold Nominal Pressure High Air Threshold <br /> psi(bar) psi(bar) psi(bar) <br /> 0 7(0,48) 10(0,69) 15(1,04) <br /> TABLED 1 7(0,48) 15(1,04) 20(1,38) <br /> HIGH/NORMAL/LOW 2 15(1,04) 20(1,38) 25(1,72) <br /> AIR PRESSURE SETTINGS FOR THE QUELL SYSTEM THAT ARE 3 16(1,04) 25(1,72) 30(2,07) <br /> COMPATIBLE WITH THE ORS 4 20(1,38) 30(2,07) 35(2,41) <br /> QUICK RELEASE SWITCH 5 25(1,72) 35(2,41) 40(2,76) <br /> 6 30(2,07) 40(2,76) 45(3,10) <br /> 7 35(2,41) 45(3,10) 50(3,45) <br /> 8 45(3,10) 55(3,79) 60(444) <br /> 9 55(3,79) 65(4,48) 70(4,83) <br /> Option 3:No Field Verification Test To transferred from line to line, creating Branchlines of nominal 4 inch(DN100) <br /> Be Performed- A 10% safety factor a grid-like scenario, as opposed to pipe size are acceptable when riser <br /> from the stipulated"Operating Times" "dead-end"branchlines which do not nipples are provided to elevate the <br /> in Tables A,B,or C must be maintained allow for air transfer. NFPA does not deflector 12 inches(305 mm)above the <br /> in the calculated results. allow for gridded dry type systems centerline of the pipe. <br /> to be installed due to the increased <br /> System Piping Layout water delivery times which can be Deflector Distance <br /> The system piping layout must be a expected. The SprinkFDT-Q software The minimum and maximum deflector <br /> "tree"configuration in order to use the program does not have the capability to distances from the ceiling shall be in <br /> SprinkFDT-O Fluid Delivery Calculation calculate fluid delivery through gridded accordance with the NEPA require- <br /> -Program and to help assure the piping systems. moots for CMSA sprinklers (Ref. <br /> quickest water delivery times. Gridded AutomaticSprinklers Section 8.11) with the exception that <br /> and looped systems are prohibitedp 8.11.4.1.2(3)(Concrete Tee Allowance) <br /> for the overhead piping system but a The Ultra K17 Upright Sprinklers are may not be applied if deflector distance <br /> looped underground may be utilized. "Control Mode Specific Application would exceed 22 inches below the <br /> (CMSA) Sprinklers Used For Storage ceiling. <br /> Note: "Tie-in drains,"where multiple Protection."Except as modified below, <br /> branchlines are drained by a common all installation requirements provided in <br /> drain line, are prohibited. While this NFPA 13,Section 8.11 apply. <br /> common line may only be nominal I <br /> inch in size, it allows for the branch- The Ultra K17 Sprinklers q7 y kre <br /> lines to"communicate"with each other. attached directly to brantblfne ess` <br /> - This "communication"allows air to be than or equal to nominal 3 inch(QN80) <br /> 411110 pipe size. <br />