Laserfiche WebLink
FIRE AND SMOKE PROTECTION FEATURES . <br /> UL 555C or shall be tested as part of a fire-resistance-rated installed on either side of the smoke barrier door <br /> floor/ceiling or roof/ceiling assembly in accordance with opening. I. ` <br /> ASTM E119 or UL 263. 3. Where a smoke damper is installed within an air J <br /> 717.3.2 Damper rating.Damper ratings shall be in actor- transfer opening in a wall, a spot-type detector <br /> dance with Sections 717.3.2.1 through 717.3.2.3. listed for releasing service shall be installed <br /> 717.3.2.1 Fire damper ratings. Fire dampers shall within 5 feet (1524 tam) horizontally of the <br /> have the minimum fire protection rating specified in damper. <br /> Table 717.3.2.1 for the type of penetration. 4. Where a smoke damper is installed in a corridor <br /> TABLE 717.3.2.1 wall or ceiling, the damper shall be permitted to <br /> FIRE DAMPER RATING be controlled by a smoke detection system <br /> MINIMUM installed in the corridor. <br /> TYPE OF DAMPER <br /> PENETRATION RATING <br /> (hours)PER Where a total-coverage smoke detector system is <br /> provided within areas served by a heating, venti- <br /> Less than 3-hour fire-resistance-rated assemblies 1.5 lation and air-conditioning (HVAC) system, <br /> 3-hour or greater fire-resistance-rated assemblies 3 smoke dampers shall be permitted to be con- <br /> 717.3.2.2 Smoke damper ratings. Smoke damper trolled by the smoke detection system. <br /> leakage ratings shall be Class I or II. Elevated tempera- 717.3.3.3 Combination fire/smoke damper actua- <br /> ture ratings shall not be less than 250°F(121°C). tion.Combination fire/smoke damper actuation shall be <br /> in 717.3.2.3 Combination fire/smoke damper ratings. accordance with Sections 717.3.3.1 and 717.3.3.2. <br /> Combination fire/smoke dampers shall have the mini- Combination fire/smoke dampers installed in smoke <br /> mum fire protection rating specified for fire dampers in control system shaft penetrations shall not be activated <br /> by local area smoke detection unless it is secondary to <br /> Table 717.3.2.1 for the type of penetration and shall <br /> also have a minimum smoke damper rating as specified the smoke management system controls. <br /> in Section 717.3.2.2. 717.3.3.4 Ceiling radiation damper actuation. The <br /> 717.3.3 Damper actuation. Damper actuation shall be in operating temperature of a ceiling radiation damper <br /> accordacordance with Sections 717.3.3.1 through 717.3.3.4 as actuation device shall be 50°F(27.8°C) above the nor- <br /> mat temperature within the duct system, but not less <br /> than 160°F(71°C). <br /> 717.3.3.1 Fire damper actuation device. The fire 717.4 Access and identification. Fire and smoke dampers <br /> damper actuation device shall meet one of the follow- shall be provided with an approved means of access,which is <br /> ing requirements: large enough to permit inspection and maintenance of the <br /> I. The operating temperature shall be approxi- damper and its operating parts.The access shall not affect the <br /> mately 50°F (10°C) above the normal tempera- integrity of fire-resistance-rated assemblies.The access open- <br /> ture within the duct system, but not less than ings shall not reduce the fire-resistance rating of the assem- <br /> 160°F(71°C). bly. Access points shall be permanently identified on the <br /> 2. The operating temperature shall be not more than exterior by a label having letters not less than '/a inch (12.7 <br /> 350°F(177°C) where located in a smoke control nun) in height reading: FIRE/SMOKE DAMPER, SMOKE <br /> system complying with Section 909. DAMPER or FIRE DAMPER.Access doors in ducts shall be <br /> tight fitting and suitable for the required duct construction. <br /> 717.3.3.2 Smoke damper actuation. The smoke <br /> damper shall close upon actuation of a listed smoke 717.5 Where required. Fire dampers, smoke dampers and <br /> detector or detectors installed in accordance with Sec- <br /> combination fire/smoke dampers shall be provided at the <br /> locations prescribed in Sections 717.5.1 through 717.5.7 and <br /> lion 907.3 and one of the following methods, as appG- <br /> cable: 717.6.Where an assembly is required to have both fire damp- <br /> ers and smoke dampers,combination fire/smoke dampers or a <br /> 1. Where a smoke damper is installed within a duct, fire damper and a smoke damper shall be required. <br /> a smoke detector shall be installed in the duct <br /> within 5 feet (1524 tam) of the damper with no 717.5.1 Fire walls. Ducts and air transfer openings per- <br /> air outlets or inlets between the detector and the per- <br /> mitted in fire walls in accordance with Section 706.11 <br /> damper. The detector shall be listed for the air shall be protected with listed fire dampers installed in <br /> velocity,temperature and humidity anticipated at accordance with their listing. <br /> the point where it is installed. Other than in 717.5.1.1 Horizontal exits. A listed smoke damper <br /> mechanical smoke control systems, dampers designed to resist the passage of smoke shall be pro- <br /> shall be closed upon fan shutdown where local vided at each point a duct or air transfer opening pene- <br /> smoke detectors require a minimum velocity to mates a fire wall that serves as a horizontal exit. <br /> operate. 717.5.2 Fire barriers. Ducts and air transfer openings of <br /> 2. Where a smoke damper is installed above smoke fire barriers shall be protected with approved fire dampers l <br /> barrier doors in a smoke barrier, a spot-type installed in accordance with their listing. Ducts and air <br /> detector listed for releasing service shall be transfer openings shall not penetrate enclosures for stair- <br /> 148 2014 OREGON STRUCTURAL SPECIALTY CODE <br />