Laserfiche WebLink
FIRE AND SMOKE PROTECTION FEATURES <br /> 2. Draftstopping is not required in buildings 718.5 Combustible materials in concealed spaces in Type I <br /> equipped throughout with an automatic sprinkler or II construction. Combustible materials shall not be per- <br /> system in accordance with Section 903.3.1.2, mitted in concealed spaces of buildings of Type I or II con- <br /> provided that automatic sprinklers are also stmction. <br /> installed in the combustible concealed spaces Exceptions: <br /> where the draftstopping is being omitted. <br /> 718.3.3 Other groups.In other groups,draftstopping shall 1. Combustible materials in accordance with Section <br /> be installed so that horizontal floor areas do not exceed 603' <br /> 1,000 square feet(93 m'). 2. Combustible materials exposed within plenums <br /> Exception: Draftstopping is not required in buildings complying with Section 602 of the Mechanical <br /> equipped throughout with an automatic sprinkler sys- Code. <br /> tem in accordance with Section 903.3.1.1. 3. Class A interior finish materials classified in accor- <br /> 718.4 Draftstopping in attics. In combustible construction, dance with Section 803. <br /> draftstopping shall be installed to subdivide attic spaces and 4. Combustible piping within partitions or shaft enclo- <br /> concealed roof spaces in the locations prescribed in Sections sures installed in accordance with the provisions of <br /> 718.4.2 and 718.4.3. Ventilation of concealed roof spaces this code. <br /> shall be maintained in accordance with Section 1203.2. 5. Combustible piping within concealed ceiling spaces <br /> 718.4.1 Draftstopping materials. Materials utilized for installed in accordance with the Mechanical Code <br /> draftstopping of attic spaces shall comply with Section and the Plumbing Code. <br /> 718.3.E 6. Combustible insulation and covering on pipe and <br /> 718.4.1.1 Openings.Openings in the partitions shall be tubing, installed in concealed spaces other than Me- <br /> protected by self closing doors with automatic latches nums,complying with Section 720.7. <br /> constructed as required for the partitions. <br /> 718.4.2 Groups R-1 and R-2.Draftstopping shall be pro- SECTION 719 <br /> vided in attics, mansards, overhangs or other concealed FIRE-RESISTANCE <br /> roof spaces of Group R-2 buildings with three or more REQUIREMENTS FOR PLASTER <br /> dwelling units and in all Group R-1 buildings. Draftstop- <br /> ping shall be installed above, and in line with, sleeping 719.1 Thickness of plaster The minimum thickness of gyp- <br /> unit and dwelling unit separation walls that do not extend sum plaster or Portland cement plaster used in a fire-resis- <br /> to the underside of the roof sheathing above. tance-rated system shall be determined by the prescribed fire <br /> Exceptions: tests.The plaster thickness shall be measured from the face of <br /> the lath where applied to gypsum lath or metal lath. <br /> I. Where corridor walls provide a sleeping unit or 719.2 Plaster equivalents. For fire-resistance purposes, 4, <br /> dwelling unit separation,draftstopping shall only inch (12.7 rum <br /> be required above one of the corridor walls. �) of unsanded gypsum plaster shall be deemed <br /> equivalent to /,,inch(19.1 rum)of one-to-three gypsum sand <br /> 2. Draftstopping is not required in buildings plaster or 1 inch(25 mm)of Portland cement sand plaster. <br /> equipped throughout with an automatic sprinkler 719.3 Noncombustible furring.In buildings of Type I and II <br /> system in accordance with Section 903.3.1.1. construction, plaster shall be applied directly on concrete or <br /> 3. In occupancies in Group R-2 that do not exceed masonry or on approved noncombustible plastering base and <br /> four stories above grade plane, the attic space fuming. <br /> shall be subdivided by draf[stops into areas not 719.4 Double reinforcement.Plaster protection more than 1 <br /> exceeding 3,000 square feet (279 m') or above inch (25 rum) in thickness shall be reinforced with an addi- � <br /> every two dwelling units,whichever is smaller. tional layer of approved lath embedded at least'/a inch(19.1 <br /> 4. Draftstopping is not required in buildings nun)from the outer surface and fixed securely in place. <br /> equipped throughout with an automatic sprinkler Exception: Solid plaster partitions or where otherwise <br /> system in accordance with Section 903.3.1.2, determined by fire tests. <br /> provided that automatic sprinklers are also <br /> installed in the combustible concealed space 719.5 Plaster alternatives for concrete. In reinforced con- <br /> where the draftstopping is being omitted. Crete construction,gypsum plaster or Portland cement plaster <br /> 718.4.3 Other groups.Draftstopping shall be installed in is permitted to be substituted for 4, inch (12.7 nun) of the <br /> attics and concealed roof spaces, such that any horizontal required poured concrete protection, except that a minimum <br /> area does not exceed roof square feet(279 m�, thickness of /s inch(9.5 nun)of poured concrete shall be pro- <br /> vided in reinforced concrete floors and 1 inch (25 rum) in <br /> (C Exception: Draftstopping is not required in buildings reinforced concrete columns in addition to the plaster finish. <br /> equipped throughout with an automatic sprinkler sys- The concrete base shall be prepared in accordance with Sec- <br /> tem in accordance with Section 903.3.1.1. tion 2510.7. <br /> 2019 OREGON STRUCTURAL SPECIALTY CODE 153 <br />