FIRE AND SMOKE PROTECTION FEATURES <br /> cally tested in the form and manner intended for use to 2. Fireblocking shall not be required where the <br /> demonstrate its ability to remain in place and to retard exterior wall covering is installed on noncombus- i �S <br /> the spread of fire and hot gases. tible framing and the face of the exterior wall <br /> 718.2.1.4 Fireblocking integrity.The integrity of fire- covering exposed to the concealed space is cov- <br /> blocks shall be maintained. ered by one of the following materials: <br /> 718.2.1.5 Double stud walls.Batts or blankets of min- 2.1. Aluminum having a minimum thickness <br /> eral or glass fiber or other approved nonrigid materials of 0.019 inch(0.5 nun). <br /> shall be allowed as fireblocking in walls constructed 2.2. Corrosion-resistant steel having a base <br /> using parallel rows of studs or staggered studs. metal thickness not less than 0.016 inch <br /> 718.2.2 Concealed wall spaces. Fireblocking shall be (0.4 mm)at any point. <br /> provided in concealed spaces of stud walls and partitions, 2.3. Other approved noncombustible materials. • <br /> including furred spaces,and parallel rows of studs or stag- 3. Fireblocking shall not be required where the <br /> gered studs,as follows: exterior wall covering has been tested in accor- <br /> 1. Vertically at the ceiling and floor levels. dance with,and complies with the acceptance cri- <br /> 2. Horizontally at intervals not exceeding 10 feet(3048 tech of, NFPA 285. The exterior wall covering <br /> nun) shall be installed as tested in accordance with <br /> NFPA 285. <br /> 718.2.3 Connections between horizontal and vertical 718.2.7 Concealed sleeper spaces. Where wood sleepers <br /> spaces.Fireblocking shall be provided at interconnections are used for laying wood flooring on masonry or concrete <br /> between concealed vertical stud wall or partition spaces fire-resistance-rated floors, the space between the floor <br /> and concealed horizontal spaces created by an assembly of slab and the underside of the wood flooring shall be filled <br /> floor joists or trusses, and between concealed vertical and with an approved material to resist the free passage of <br /> horizontal spaces such as occur at soffits, drop ceilings, flame and products of combustion or fireblocked in such a <br /> cove ceilings and similar locations. manner that there will be no open spaces under the floor- <br /> 718.2.4 Stairways.Fireblocking shall be provided in con- ing that will exceed 100 square feet (9.3 m2) in area and <br /> cealed spaces between stair stringers at the top and bottom such space shall be filled solidly under permanent parti- <br /> of the run. Enclosed spaces under stairs shall also comply tions so that there is no communication under the flooring <br /> with Section 1009.9.3. between adjoining rooms. <br /> 718.2.5 Ceiling and floor openings. Where required by Exceptions: <br /> Section 712.1.7, Exception 1 of Section 714.4.1.2 or Sec- I. Fireblocking is not required for slab-on-grade <br /> tion 714.4.2, fireblocking of the annular space around floors in gymnasiums. <br /> vents,pipes,ducts,chimneys and fireplaces at ceilings and <br /> floor levels shall be installed with a material specifically 2. Fireblocking is required only at the juncture of <br /> tested in the form and manner intended for use to demon- each alternate lane and at the ends of each lane in <br /> grate its ability to remain in place and resist the free pas- a bowling facility. <br /> sage of flame and the products of combustion. 718.3 Draftstopping in floors. In combustible construction, <br /> 718.2.5.1 Factory-built chimneys and fireplaces. draftstopping shall be installed to subdivide floor/ceiling <br /> Factory-built chimneys and fireplaces shall be fife- assemblies in the locations prescribed in Sections 718.3.2 <br /> blocked in accordance with UL 103 and UL 127. through 718.3.3. <br /> 718.2.6 Exterior wall coverings. Fireblocking shall be 718.3.1 Draftstopping materials.Draftstopping materials <br /> installed within concealed spaces of exterior wall cover- shall not be less than 1/,-inch(12.7 mm)gypsum board, /a <br /> ings and other exterior architectural elements where per- inch (9.5 rum) wood structural panel, 3/8-inch (9.5 mm) <br /> miffed to be of combustible construction as specified in particleboard, 1-inch (25-rum) nominal lumber, cement <br /> Section 1406 or where erected with combustible frames. fiberboard,batts or blankets of mineral wool or glass fiber, <br /> Fireblocking shall be installed at maximum intervals of 20 or other approved materials adequately supported. The <br /> feet(6096 rum)in either dimension so that there will be no integrity of draftstops shall be maintained. <br /> concealed space exceeding 100 square feet (9.3 m2) 718.3.2 Groups R-1, R-2, R-3 and R-4. Draftstopping <br /> between fireblocking.Where wood furring strips are used, shall be provided in floor/ceiling spaces in Group R-1 <br /> they shall be of approved wood of natural decay resistance buildings, in Group R-2 buildings with three or more <br /> or preservative-treated wood. If noncontinuous, such.ele- dwelling units, in Group R-3 buildings with two dwelling <br /> ments shall have closed ends, with at least 4 inches (102 units and in Group R-4 buildings. Draftstopping shall be <br /> nun)of separation between sections. located above and in line with the dwelling unit and sleep- <br /> Exceptions: ing unit separations. <br /> 1. Fireblocking of cornices is not required in single- Exceptions: / <br /> family dwellings. Fireblocking of cornices of a 1. Draftstopping is not required in buildings <br /> two-family dwelling is required only at the line of equipped throughout with an automatic sprinkler <br /> dwelling unit separation. system in accordance with Section 903.3.1.1. <br /> 152 2014 OREGON STRUCTURAL SPECIALTY CODE <br />