• FIRE AND SMOKE PROTECTION FEATURES <br /> time period equivalent to the fire-resistance rat- 717.7 Flexible ducts and air connectors.Flexible ducts and <br /> c ing of the construction penetrated. air connectors shall not pass through any fire-resistance-rated <br /> 5. Grille openings located in a ceiling of a fie-resin- assembly. Flexible air connectors shall not pass through any <br /> tance-rated floor/ceiling or roof/ceiling assembly wall,floor or ceiling. <br /> shall be protected with a listed ceiling radiation <br /> damper installed in accordance with Section SECTION 718 <br /> 717.6.2.1. <br /> CONCEALED SPACES <br /> 717.6.2 Membrane penetrations. Ducts and air transfer <br /> openings constructed of approved materials in accordance 718.1 General.combustible <br /> Fireblocking and locationsdra in accordance shall be <br /> with the Mechanical Code that penetrate the ceiling mem- installed in combustible concealed in <br /> brane of a fire-resistance-rated floor/ceiling or roof/ceiling wnh this section. FirebLo or/ce shall comply with Section <br /> assembly shall be protected with one of the following: 718.2.complyDraftstopping in floor/ceiling spaces and attic spaces <br /> shad with Sections 718.3 and 718.4, respectively. <br /> 1. A shaft enclosure in accordance with Section 713. The permitted use of combustible materials in concealed <br /> 2. A listed ceiling radiation damper installed at the spaces of buildings of Type I or II construction shall be lim- <br /> ceiling line where a duct penetrates the ceiling of a iced to the applications indicated in Section 718.5. <br /> fire-resistance-rated floor/ceiling or roof/ceiling 718.2 Fireblocking. In combustible construction,fireblock- <br /> assembly. ing shall be installed to cut off concealed draft openings(both <br /> 3. A listed ceiling radiation damper installed at the vertical and horizontal) and shall form an effective bather <br /> ceiling line where a diffuser with no duct attached between floors,between a top story and a roof or attic space. <br /> penetratesthe ceiling of a fire-resistance-rated floor/ Freblocking shall be installed in the locations specified in <br /> ceiling or roof/ceiling assembly. Sections 718.2.2 through 718.27. <br /> 717.6.2.1 Ceiling radiation dampers. Ceiling radio- 718.2.1 Fireblocking materials. Fireblocking shall con- <br /> tion dampers shall be tested in accordance with Section sist of the following materials: <br /> 717.3.1. Ceiling radiation dampers shall be installed in 1. Two-inch(51 mm)nominal lumber. <br /> accordance with the details listed in the fire-resistance- 2. Two thicknesses of I-inch(25 mm)nominal lumber <br /> rated assembly and the manufacturer's installation with broken lap joints. <br /> %4,,,,, instructions and the listing. Ceiling radiation dampers <br /> are not required where either of the following applies: 3. One thickness of 0.719-inch(18.3 mm) wood struc- <br /> tural panels with joints backed by 0.719-inch (18.3 <br /> L Tests in accordance with ASTM E 119 or UL 263 rum)wood structural panels. <br /> have shown that ceiling radiation dampers are <br /> not necessary in order to maintain the fire-resis- 4. One thickness of 0.75-inch(19.1 mm)particleboard <br /> tance rating of the assembly. with joints backed by 0.75-inch (19 mm) particle- <br /> board. <br /> 2. Where exhaust duct penetrations are protected in 5. One-half-inch(12.7 mm)gypsum board. <br /> accordance with Section 714.4.1.2, are located <br /> within the cavity of a wad and do not pass 6. One-fourth-inch(6.4 rum)cement-based millboard. <br /> through another dwelling unit or tenant space. 7. Batts or blankets of mineral wool, mineral fiber or <br /> 717.6.3 Nonfire-resistance-rated floor assemblies. Duct other approved materials installed in such a manner <br /> systems constructed of approved materials in accordance as to be securely retained in place. <br /> with the Mechanical Code that penetrate nonfire-resis- : <br /> tance-rated floor assemblies shall be protected by any of 8. Cellulose insulation installed as tested for the see- <br /> the following methods: cific application. <br /> 1. A shaft enclosure in accordance with Section 713. 718.2.1.1 Batts or blankets of mineral wool or min- <br /> eral fiber.Batts or blankets of mineral wool or mineral <br /> 2. The duct connects not more than two stories,and the fiber or other approved nonrigid materials shall be per- <br /> annular space around the penetrating duct is pro- mitted for compliance with the 10-foot(3048 nun)hor- <br /> tected with an approved noncombustible material izontal fireblocking in walls constructed using parallel <br /> that resists the free passage of flame and the prod- rows of studs or staggered studs. <br /> ucts of combustion. 718.2.1.2 Unlaced fiberglass. Unfaced fiberglass ban <br /> 3. The duct connects not more than three stories, and insulation used as fireblocking shall fill the entire cross <br /> the annular space around the penetrating duct is section of the wall cavity to a minimum height of 16 <br /> protected with an approved noncombustible mate- inches(406 rum)measured vertically.When piping,con- <br /> rial that resists the free passage of flame and the duit or similar obstructions are encountered, the insula- <br /> w products of combustion and a fire damper is tion shall be packed tightly around the obstruction. <br /> installed at each floor line. 718.2.1.3 Loose-fill insulation material. Loose-fill <br /> Exception: Fire dampers are not required in insulation material, insulating foam sealants and caulk <br /> ducts within individual residential dwelling units. materials shall not be used as a fireblock unless specifi- <br /> 2014 OREGON STRUCTURAL SPECIALTY CODE 151 <br />