FIRE AND SMOKE PROTECTION FEATURES <br /> 3.2. The duct shall be constructed of steel a point a duct or air transfer opening penetrates a smoke bar- <br /> minimum of 0.0217 inch (0.55 mm) in rier. Smoke dampers and smoke damper actuation meth- <br /> thickness. ods shall comply with Section 717.3.3.2. <br /> 3.3. The duct shall not have openings that Exception: Smoke dampers are not required where the <br /> communicate the corridor with adjacent openings in ducts are limited to a single smoke corn- <br /> spaces or rooms. partment and the ducts are constructed of steel. <br /> 3.4. The duct shall be installed above a ceil- 717.5.6 Exterior walls.Ducts and air transfer openings in <br /> ing. fire-resistance-rated exterior walls required to have pro- <br /> 3.5. The duct shall not terminate at a wall reg- tected openings in accordance with Section 705.10 shall <br /> ister in the fire-resistance-rated wall. be protected with listed fire dampers installed in accor- <br /> dance with their listing. <br /> 3.6. A minimum 12-inch-long (305 mm) by 717.5.7 Smoke partitions. A listed smoke damper <br /> 0.060-inch-thick (1.52 mm) steel sleeve designed to resist the passage of smoke shall be provided <br /> shall be centered in each duct opening. <br /> The sleeve shall be secured to both sides at each point that an air transfer opening penetrates a <br /> of the wall and all four sides of the sleeve smoke partition.Smoke dampers and smoke damper actua- <br /> tion methods shall comply with Section 717.3.3.2. <br /> with minimum 1'/2-inch by 14,inch by <br /> 0.060-inch (38 mm by 38 nun by 1.52 Exception: Where the installation of a smoke damper <br /> mm) steel retaining angles. The retaining will interfere with the operation of a required smoke <br /> angles shall be secured to the sleeve and control system in accordance with Section 909, <br /> the wall with No. 10 (M5) screws. The approved alternative protection shall be utilized. <br /> annular space between the steel sleeve 717.6 Horizontal assemblies. Penetrations by ducts and air <br /> and the wall opening shall be filled with transfer openings of a floor, floor/ceiling assembly or the <br /> mineral wool batting on all sides. ceiling membrane of a roof/ceiling assembly shall be pro- <br /> 4. Such walls are penetrated by ducted HVAC sys- tected by a shaft enclosure that complies with Section 713 or <br /> tems, have a required fire-resistance rating of 1 shall comply with Sections 717.6.1 through 717.6.3. <br /> hour or less, and are in buildings equipped 717.6.1 Through penetrations.In occupancies other than <br /> throughout with an automatic sprinkler system in Groups I-2 and I-3,a duct constructed of approved materi- <br /> accordance with Section 903.3.1.1 or 903.3.1.2. als in accordance with the Mechanical Code that pene- [ ] <br /> For the purposes of this exception, a ducted trates a fire-resistance-rated floor/ceiling assembly that �/ <br /> HVAC system shall be a duct system for convey- connects not more than two stories is permitted without <br /> ing supply, return or exhaust air as part of the shaft enclosure protection,provided a listed fire damper is <br /> structure's HVAC system. Such a duct system installed at the floor line or the duct is protected in accor- <br /> shall be constructed of sheet steel not less than dance with Section 714.4. For air transfer openings, see <br /> No. 26 gage thickness and shall be continuous Section 712.1.8. <br /> from the air-handling appliance or equipment to Exception:A duct is permitted to penetrate three floors <br /> the air outlet and inlet terminals. or less without a fire damper at each floor, provided <br /> 717.5.4.1 Corridors. A listed smoke damper designed such duct meets all of the following requirements: <br /> to resist the passage of smoke shall be provided at each I. The duct shall be contained and located within <br /> point a duct or air transfer opening penetrates a corn- the cavity of a wall and shall be constructed of <br /> dor enclosure required to have smoke and draft control steel having a minimum wall thickness of 0.0187 <br /> doors in accordance with Section 716.5.3. inches(0.4712 min)(No. 26 gage). <br /> Exceptions: 2. The duct shall open into only one dwelling or <br /> 1. Smoke dampers are not required where the sleeping unit and the duct system shall be contin- <br /> building is equipped throughout with an uous from the unit to the exterior of the building. <br /> approved smoke control system in accordance 3. The duct shall not exceed 4-inch(102 mm)nomi- <br /> with Section 909, and smoke dampers are not nal diameter and the total area of such ducts shall <br /> necessary for the operation and control of the not exceed 100 square inches (0.065 m') in any <br /> system. 100 square feet(9.3 m')of floor area. <br /> 2. Smoke dampers are not required in corridor 4. The annular space around the duct is protected <br /> penetrations where the duct is constructed of with materials that prevent the passage of flame <br /> steel not less than 0.019 inch (0.48 nun) in and hot gases sufficient to ignite cotton waste <br /> thickness and there are no openings serving where subjected to ASTM E 119 or UL 263 time- <br /> the corridor. temperature conditions under a minimum posi- <br /> 717.5.5 Smoke barriers.A listed smoke damper designed tive pressure differential of 0.01 inch(2.49 Pa)of / <br /> to resist the passage of smoke shall be provided at each water at the location of the penetration for the <br /> 150 2014 OREGON STRUCTURAL SPECIALTY CODE <br />