• FIRE AND SMOKE PROTECTION FEATURES <br /> SECTION 710 SECTION 711 <br /> thr I SMOKE BARRIERS SMOKE PARTITIONS <br /> 710.1General.Smoke barriers shall comply with this section. 711.1 General. Smoke partitions installed as required else <br /> where in the code shall comply with this section. <br /> 710.2 Materials.Smoke barriers shall be of materials permit- 711.2 Materials.The walls shall be of materials permitted by <br /> ted by the building type of construction. the building type of construction. <br /> 710.3 Fire-resistance rating.A 1-hour fir resistancerating 711.3 Fire-resistance rating.Unless required elsewhere in the <br /> is required for smoke barriers. code,smoke partitions are not required to have afire-resistance <br /> rating. <br /> Exception: Smoke barriers constructed of minimum <br /> 0.10-inch-thick(2.5 tom)steel in Group I-3 buildings. 711.4 Continuity.Smoke partitions shall extend from the top <br /> of the foundation or floor below to the underside of the floor or <br /> 710.4 Continuity. Smoke barriers shall form an effective roof sheathing, deck or slab above or to the underside of the <br /> membrane continuous from outside wall to outside wall and ceiling above where the ceiling membrane is constructed to <br /> from the top of the foundation or floor/ceiling assembly below limit the transfer of smoke. <br /> to the underside of the floor or roof sheathing, deck or slab 71/5 Openings.Windows shall be sealed to resist the free pas- <br /> above,including continuity through concealed spaces,such as sage of smoke or be automatic-closing upon detection of smoke. <br /> those found above suspended ceilings, and interstitial strut- Doors in smoke partitions shall comply with this section. <br /> tural and mechanical spaces.The supporting construction shall <br /> be protected to afford the required fire-resistance rating of the 711.5.1 Louvers. Doors in smoke partitions shall not <br /> wall or floor supported in buildings of other than Type IIB,111B include louvers. <br /> or VB construction. 711.5.2 Smoke and draft control doors. Where required <br /> Exception:Smoke-barrier walls are not required intersti- elsewhere in the code,doors in smoke partitions shall meet <br /> tial spaces where such spaces are designed and constructed the requirements for a smoke and draft control door assem- <br /> with ceilings that provide resistance to the passage of fire bly tested in accordance with UL 1784.The air leakage rate <br /> and smoke equivalent to that provided by the smoke-barrier of the door assembly shall not exceed 3.0 cubic feet per min- <br /> walls. ute per square foot(0.015424 m'/(s-m2))of door opening at <br /> 44hoy 0.10 inch(24.9 Pa)of water for both the ambient tempera- <br /> 710.5 Openings. Openings in a smoke barrier shall be pro- tore test and the elevated temperature exposure test.Installa- <br /> tected in accordance with Section 715. tion of smoke doors shall be in accordance withNFPA 105. <br /> Exceptions: 711.53 Self-or automatic-closing doors.Where required <br /> elsewhere in the code, doors in smoke partitions shall be <br /> I. In Group 1-2,where doors are installed across corri- self-or automatic-closing by smoke detection in accordance <br /> dors,a pair of opposite-swinging doors without acen- with Section 715.4.8.3. <br /> ter mullion shall be installed having vision panels <br /> with fire-protection-rated glazing materials in 711.6 Penetrations and joints.The space around penetrating <br /> fire-protection-rated frames, the area of which shall items and in joints shall be filled with an approved material to <br /> not exceed that tested.The doors shall be close fitting limit the free passage of smoke. <br /> within operational tolerances, and shall not have 711.7 Ducts and air transfer openings.The space around a <br /> undercuts in excess of V4 inch,louvers or grilles.The duct penetrating a smoke partition shall be filled with an <br /> doors shall have head and jamb stops, astragals or approved material to limit the free passage of smoke.Air trans- <br /> rabbets at meeting edges and shall be automatic-clos- fer openings in smoke partitions shall be provided with a smoke <br /> ing by smoke detection in accordance with Section damper complying with Section 716.3.2.2. <br /> 715.4.8.3. Where permitted by the door manufac- Exception:Where the installation of a smoke damper will <br /> turer's listing, positive-latching devices are not <br /> required interfere with the operation of a required smoke control sys- <br /> tem in accordance with Section 909, approved alternative <br /> 2. In Group 1-2, horizontal sliding doors installed in protection shall be utilized. <br /> accordance with Section 1008.1 4.3 and protected in <br /> accordance with Section 715. <br /> 710.6 Penetrations.Penetrations of smoke barriers shall com- SECTION 712 <br /> ply with Section 713. HORIZONTAL ASSEMBLIES <br /> 712.1 General.Floor and roof assemblies required to have a <br /> 710.7 Joints.Joints made in or between smoke barriers shall <br /> fire-resistance rating shall comply with this section. <br /> comply with Section 714. Nonfrre-resistance-rated floor and roof assemblies shall com- <br /> 710.8 Ducts and air transfer openings. Penetrations in a ply with Section 713.4.2. <br /> smoke barrier by ducts and air transfer openings shall comply 712.2 Materials. The floor and roof assemblies shall be of <br /> with Section 716. materials permitted by the building type of construction. <br /> 2010 OREGON STRUCTURAL SPECIALTY CODE 115 <br />