FIRE AND SMOKE PROTECTION FEATURES <br /> 712.3 Fire-resistance rating. The fire-resistance rating of 712.5 Penetrations. Penetrations of horizontal assemblies <br /> floor and roof assemblies shall not be less than that required by shall comply with Section 713. <br /> the building type of construction Where the floor assembly 712.6 Joints.Joints made in or between horizontal assemblies <br /> separates mixed occupancies, the assembly shall have a shall comply with Section 714.The void created at the intersec- <br /> fire-resistance rating of not less than that required by Section lion of a floor/ceiling assembly and an exterior curtain wall <br /> 508.4 based on the occupancies being separated. Where the assembly shall be protected in accordance with Section 714.4. <br /> floor assembly separates a single occupancy into different fire <br /> areas, the assembly shall have a fire-resistance rating of not 712.7 Ducts and air transfer openings.Penetrations in hori- <br /> less than that required by Section 707.3.9.Horizontal assem- zontal assemblies by ducts and air transfer openings shall corn- <br /> blies separating dwelling units in the same building and hori- ply with Section 716. <br /> zontal assemblies separating sleeping units in the same 712.5 Floor fire door assemblies.Floor fire door assemblies <br /> building shall be a minimum of 1-hour fire-resistance-rated used to protect openings in fne-resistance-rated floors shall be <br /> construction. tested in accordance with NFPA 288, and shall achieve a <br /> Exception:Dwelling unit and sleeping unit separations in fire-resistance rating not less than the assembly being pene- <br /> buildings of Type UB,UM and VB construction shall have trated. Floor fire door assemblies shall be labeled by an <br /> fire-resistance ratings of not less than 4,hour in buildings approved agency. The label shall be permanently affixed and <br /> equipped throughout with an automatic sprinkler system in shall specify the manufacturer, the test standard and the <br /> accordance with Section 903.3.1.1. fire-resistance rating. <br /> 712.3.1 Ceiling panels.Where the weight of lay-in ceiling 712.9 Smoke barrier. Where horizontal assemblies are <br /> panels,used as part of fire-resistance-rated floor/ceiling or required to resist the movement of smoke by other sections of <br /> roof/ceiling assemblies,is not adequate to resist an upward this code in accordance with the definition of smoke barrier, <br /> force of 1 pound per square foot (48 Pa), wire or other penetrations and joints in such horizontal assemblies shall be <br /> approved devices shall be installed above the panels to pre- protected as required for smoke barriers in accordance with <br /> vent vertical displacement under such upward force. Sections`7J35'a49914.6.kkegardless of the number of stories <br /> 7123.2 Access doors. Access doors shall be permitted in connected by elevator shaft enclosures,doors located in eleva- <br /> ceilings of fire-resistance-rated Boodceiling and rooflceil- tor shaft enclosures that penetrate the horizontal assembly shall <br /> ing assemblies provided such doors are tested in accordance be protected by enclosed elevator lobbies complying with Sec- <br /> with ASTM E 119 or UL 263 as horizontal assemblies and tion'70&141t1.0penings through horizontal assemblies shall <br /> labeled by an approved agency for such purpose. be protected by shaft enclosures complying with Section 708. <br /> Horizontal assemblies shall not be allowed to have unprotected �/ <br /> 712.3.3 Unusable space. In 1-hour fire-resistance-rated vertical openings. <br /> floor assemblies,the ceiling membrane is not required to be <br /> installed over unusable crawl spaces. In 1-hour fire-resis- <br /> tance-rated roof assemblies, the floor membrane is not SECTION 713 <br /> required to be installed where unusable attic space occurs PENETRATIONS <br /> above. 713.1 Scope.The provisions of this section shall govern the <br /> 712.4 Continuity. Assemblies shall be continuous without materials and methods of construction used to protect through <br /> openings,penetrations or joints except as permitted by this sec- penetrations and membrane penetrations of horizontal assem- <br /> lion and Sections 708.2,713 4,714 and 1022.1.Skylights and Mies and fire-resistance-rated wall assemblies. <br /> other penetrations through a fire-resistance-rated roof deck or <br /> slab are permitted to be unprotected, provided that the strut- 713.1.1 Ducts and air transfer openings.Penetrations of <br /> tural integrity of the tire-resistance-rated roof assembly is fire-resistance-rated walls by ducts that are not protected <br /> maintained. Unprotected skylights shall not be permitted in with dampers shall comply with Sections 713.2 through <br /> roof assemblies required to be fire-resistance rated in actor- <br /> 713.33. Penetrations of horizontal assemblies not pro- <br /> dance with Section 704.10. The supporting construction shall tooted with a shaft as permitted by Exception 4 of Section <br /> be protected to afford the required fire-resistance rating of the 708.2,and not required to be protected with fire dampers by <br /> horizontal assembly supported. other sections of this code,shall comply with Sections 713.4 <br /> through 713.4.2.2.Ducts and air transfer openings that are <br /> Exception:In buildings of Type IID,RIB or VB construe- protected with dampers shall comply with Section 716. <br /> tion,the construction supporting the horizontal assembly is <br /> not required to be fire-resistance-rated at the following: 713.2 Installation details.Where sleeves are used, they shall <br /> be securely fastened to the assembly penetrated. The space <br /> 1. Horizontal assemblies at the separations of incidental between the item contained in the sleeve and the sleeve itself <br /> uses as specified by Table 508.2.5, provided the and any space between the sleeve and the assembly penetrated <br /> required fire-resistance rating does not exceed I shall be protected in accordance with this section. Insulation <br /> hour. and coverings on or in the penetrating item shall not penetrate <br /> 2. Horizontal assemblies at the separations of dwelling the assembly unless the specific material used has been tested C <br /> units and sleeping units as required by Section 420.3. as part of the assembly in accordance with this section. <br /> 3. Horizontal assemblies at smoke barriers constructed 713.3 Fire-resistance-rated walls. Penetrations into or <br /> in accordance with Section 710. through fire walls,fire barriers, smoke barrier walls and fire <br /> 116 2010 OREGON STRUCTURAL SPECIALTY CODE <br />