Laserfiche WebLink
4 PROPOSED STRATEGY <br /> In lieu of the required 2-hour fire-resistance rating at the north and east exterior walls of BG3H, it <br /> is proposed to provide the following: <br /> Water Curtain at North and East Exterior Walls: Provide "water curtain' as listed below. The <br /> discharge on the interior shall be calculated with the simultaneous demand of the overhead fire <br /> sprinkler system as detailed in NFPA 13. <br /> North Wall Exterior: Provide closely-spaced sprinklers (water curtain) at 6 ft on-center <br /> maximum spacing per NFPA 13. Sprinklers to be 200°F, dry barrel, upright sprinklers <br /> installed in the horizontal spray orientation. These sprinklers will be located at the top of <br /> the exterior wall, 12 inches away. The discharge of these sprinklers will develop a spray <br /> pattern back at the protected wall. <br /> North Wall Interior: Provide closely-spaced sprinklers (water curtain) at 6 ft on-center <br /> maximum spacing per NFPA 13. Sprinklers to be 155°F, upright or pendant standard spray <br /> sprinklers. These sprinklers will be installed within 12 inches of the roof, at 12 to 24 inches <br /> from the wall. The discharge of these sprinklers will develop a spray pattern along the <br /> protected wall. <br /> East Wall Exterior: No protection provided. <br /> East Wall Interior: Provide closely-spaced sprinklers (water curtain) at 6 ft on-center <br /> maximum spacing per NFPA 13. Sprinklers to be 155°F, upright or pendant standard spray <br /> sprinklers. These sprinklers will be installed within 12 inches of the roof, at 12 to 24 inches <br /> from the wall. The discharge of these sprinklers will develop a spray pattern along the <br /> protected wall. <br /> Non-Combustible Construction with Fire-Resistance-Rated Doors: Although the non- <br /> combustible north and east exterior walls are not constructed as a fire-resistance-rated assembly, <br /> the doors provided are self-closing, with a 90-minute fire-resistance rating. <br /> Sprinklers: The building is fully-sprinklered per NFPA 13 and the requirements of OSSC 412.3.6 <br /> Exception 2 which allows for a minimum sprinkler density of Extra Hazard Group I in lieu of foam <br /> suppression, when other building area, yard, and aircraft limitations are met. <br /> 5 EQUIVALENCY EVALUATION <br /> The installation of closely-spaced sprinklers (water curtain) provides "active" protection in lieu of, <br /> and equivalent to,the"passive" protection afforded by the use of a fire-resistance-rated assembly. <br /> The sprinklers act to cool the surface of the wall to prevent fire from progressing for the same <br /> duration. At the north wall, the sprinklers are provided on both sides since there is risk of fire from <br /> the building itself, as well as from the property to the north. However, on the east side, protection <br /> is only provided at the interior side, for a fire that originates on the interior of the building. The risk <br /> of a fire originating from the east is negligible because it fronts a public way with a major street; <br /> there are no structures,trees, or significant combustible loading in this area. In addition, per OSSC <br /> ( Section 412.3.1 in the 2018 IBC Commentary, the purpose of the 30 ft requirement is to prevent <br /> the spread of fire to"adjacent building and structures"and to allow the "fire department additional <br /> time and protection as it attempts to take control of a fire situation in a hangar". The condition at <br /> this property is such that the associated east yard is -26 ft, with the remaining 4 ft falling on a <br />