DATE/TIME <br />TYPE <br /> <br /> SITE EVALUATION/SEPTIC PERMIT <br /> 06/29/99 17:06 PERMIT NO 99-04990 <br /> SP STATUS ISSUED <br /> ISSUED 06/29/1999 <br /> TO EXPIRE 06/28/2000 <br /> PAGE 3 <br />in the area and adversely affect the septic system approval. <br />The areas of the initial septic system and the future repair <br />system must both be protected. <br />THIS SYSTEM MUST BE INSPECTED AND APPROVED PRIOR TO BACKFILL <br />When work is complete and ready for inspection, call our <br />Automated Inspection Request line at 272-4427 to request an <br />inspection. Enter the number "801" for a PRE-COVER inspec- <br />tion. You may leave a message for the inspector if desired. <br />Be sure the System Record form with the As-Built drawing is <br />on the job or in our office when the inspection is requested <br />An inspection should be completed within seven (7) days, <br />EFFLUENT SEWER: The effluent sewer is the pipe running from <br />the septic tank to the disposal field. The effluent sewer <br />shall extend at least five (5) feet from the tank, There <br />must be a minimum difference of eight (8) inches between the <br />invert (flow line) of the septic tank outlet and the invert <br />of the distribution or drop box outlet, In Equal Distribu- <br />tion, there must be six (6) inches of fall between the <br />septic tank outlet and the distribution box inlet. In Serial <br />Distribution. there must be two (2) inches of fall between <br />the septic tank outlet and the drop box inlet, <br /> <br /> <br />