, Salem Area Mass Transit District/Marion County IFB 00-03 17 <br />TAB Services <br />• Minimum design air flow. <br />• Maximum design air flow. <br />• Maximum actual air flow. <br />• Inlet static pressure. <br />• Inlet and outlet temperature at full heat. <br />• Electric Heater Coil Data: kW, voltage, phase. <br />2) DUCT PRESSURE SENSOR (VAV SYSTEM) TESTING <br />• Location. <br />• Static pressure with fan at block load airflow. <br />2) REFRIGERANT COOLING COIL TESTING <br />• Identification/number. <br />• Location. <br />• Service. <br />• Manufacturer. <br />• Airflow, design and actuaL • <br />• Entering air DB temperature, deign and actual. <br />• Entering air WB temperature, design and actual. <br />• Leaving air DB temperature, design and actual. <br />• Leaving air WB temperature, design and actual. <br />• Air pressure drop, design and actual. <br />2) REFRIGERANT SYSTEM CONDENSING UNIT <br />• Ambient temperature. <br />• Head pressure. <br />• Suction pressure. <br />• Compressor electrical data, phase, voltage, amperage; nameplate, actual, no load. <br />Record voltage and amperage on all phases of 3-phase motors. <br />• Copy of unit manufacturer's test start-up, test report. <br />