Laserfiche WebLink
, Salem Area Mass Transit District/Marion County IFB 00-03 18 <br />TAB Services <br />2) REFRIGERANT SYSTEM HEAT PUMP AIR-AIR <br />• Ambient temperature. <br />• Head pressure. <br />• Suction pressure. <br />• Compressor electrical data, phase, voltage, amperage; nameplate, actual, no load. <br />Record voltage and amperage on all phases of 3-phase motors. <br />• Copy of unit manufacturer's test start-up, test report. <br />2) REFRIGERANT SYSTEM DUCTLESS UNITS <br />• Ambient temperature. <br />• Head pressure. <br />• Suction pressure. <br />• Compressor electrical data, phase, voltage, amperage; nameplate, actual, no load. <br />Record voltage and amperage on all phases of 3-phase motors. <br />• Copy of unit manufacturer's test start-up, test report. <br />2) ADJUSTING <br />• Recorded data shall represent actually measured or observed conditions. <br />Permanently mark settings of valves, dampers, and other adjustment devices <br />allowing settings to be restored. Set and lock memory stops. Adjust air systems to <br />deliver specified to deliver specified volumes with lowest possible fan speed. <br />2) DOMESTIC WATER <br />• Adjust domestic water recirculation system to ensure hot water circulation in all <br />mains. <br />