Harding Lawson Associates <br />4. Provide a minimum of 85% filtration, if the return air side of an HVAC system is <br />used during construction. Separate filtration media shouid be specified on any <br />permanent equipment during construction. Just prior to occupancy, new clean <br />media should be installed. Ail coils, air filters, and fans should be clean before <br />testing and balancing is done and especially before baseline air quality tests are <br />conducted. <br />Credit 4: Design of Chemical Storage Areas <br />Design all chemical storage and mixing areas for housekeeping products (both central <br />storage facilities and janitors closets) to allow for secure product storage in spaces that <br />have water in the chemical concentrate mixing areas, with drains plumbed for the <br />appropriate disposal of liquid waste, separate outside venting, and negative pressure. <br />All storage areas for housekeeping equipment and products should have separate <br />exhausts vented to the outside and should be ventilated and operable under negative <br />pressure. <br />SAFEGUARDING WATER <br />Credit 1: Water-Conserving Fixtures <br />Install fixtures that use 20% less water than the water usage requirements in the Energy <br />Policy Act of 1992 as follows: <br />Fixture Requirement 20% Reduction <br />Showerhead 2.5 allons/minute'` 2.0 allons/minute <br />Lavato Fixture 2.5 allons/minute` 2.0 allons/minute <br />Lavato re lacement aerators 2.5 allons/minute` 2.0 allons/minute <br />Kitchen faucets 2.5 allons/minute` 2.0 allons/minute <br />Kitchen re lacement aerates 2.5 allons/minute* 2.0 allons/minute <br />Meterin faucets 0.25 allons/c 0.20 allons/c <br />Gravit tank-t pe toilets 1.6 allons/flush** 1.3 atlons/flush <br />Flushometer tank toilets 1.6 allons/flush 1.3 allons/flush <br />Electromechanical h draulic toilets 1.6 allons/flush 1.3 allons/Flush <br />Blowout toilets 1.6 allons/flush 1.3 allons/flush <br />Urinals 1.0 allons/flush 0.8 allons/flush <br />" Ht tiowing water pressure ot 80 pounds per square inch. <br />"' Gravity tank type white 2-piece toilets which bear an adhesive Iabel ("Commercial Use Only") <br />manufactured after January 1, 1994 and before January 1, 1997, are 3.5 gallons/flush. <br />The specifications and drawings call for flow control devices for showers to prevent <br />fl~w ovEr 2.0 ~allons;minute and for public lavatories to prevert flow ovzr C.5 <br />gallons/minute. Also specified are infrared sensors for lavatories. The rest of the <br />fixtures do not meet the 20% reduction requirement. To obtain this credit it must be <br />shown that the total water consumption will be 20% less than it would be using <br />fixtures that meet the requirements of the Energy Policy Act of 1992. A consumption <br />calculation based on demand calculation used to determine the fixture counts and <br />piping sizes would provide this information. <br />Credit 4: Water-Efficient Landscape <br />Use only plants that are tolerant of climate, soils, and natural water availabiliry, and <br />that do not receive watering from municipal potable water after a period of <br />establishment is complete. <br />• The plants listed on Sheet L1.0 are native to this climate, however, they may <br />need to be watered after they are established. This credit can be obtained if <br />plants are selected that witl not need watering after they are established. If this is <br />c~,; <br />