Laserfiche WebLink
LERCH, BATES & ASSOCIATES INC. <br />5210 BICKFORD, SUITE 202 <br />SNOHOMISH, WA 98290-9216 <br />(425)774-3088 <br />TO: <br />ATTENTION: <br />RE: <br />CONTRACTOR: <br />FIELD ENGINEER: <br />Arbuckle Costic Architects <br />Leonard Lodder <br />Courthouse Square <br />Thyssen -Sound <br />Dale Meyers <br />FIELD REPORT: FR-1 <br />REVIEW DATE: 1ll10/00 <br />An installation review was performed. The following items were noted, requiring correction or <br />follow up by Thyssen Sound. <br />General <br />1. 14210-2.5 B-2: Anti nuisance Feature: Not working. <br />2. 14210-2.6 F: No angle, guards on hoist rope. Provide as specified. <br />3. Close out documents have not been reviewed. <br />Car Performance <br />Car #1: <br />1. Adjust the floor-to-floor performance time in both directions to 9.4 seconds. Measured <br />up time is 10.7 seconds; down time is 10.6 seconds. <br />2. Adjust the door opening time to 1.7 seconds. Measured time is 2. ~ seconds. <br />3. Adjust the door closing time to 2.4 seconds. Measured time is 3.4 seconds. <br />4. Adjust the nudging time (time doors remain open when the rays are continually <br />interrupted) to between 20.0 and 25.0 seconds. Measured time is: Not working. <br />Car #2: <br />1. Adjust the floor-to-floor performance time in both directions to 9.4 seconds. Measured <br />up time is 11.5; down time is 11.5 seconds. <br />2. Adjust the door opening time to 1.7 seconds. Measured time is 2.0 seconds. <br />3. Adjust the door closing time to 2.4 seconds. Measured time is 3.0 seconds. <br />