Laserfiche WebLink
LERCH, BATES & ASSOCIATES INC. FIELD REPORT: FR-1 <br />Re: COURTHOUSE SQUARE Page 2 <br />4. Adjust the interrupted ray time (time door remains open in response to a car call) to <br />between 3.0 and 4.0 seconds. Measured time is: Not working. <br />5. Repair door open button operation to operative at any position of door travel. During <br />closing, door hesitates at 1" from closed and door operation button is not operative. <br />Car #3 <br />1. Adjust door opening time to 1.7 seconds. Measured time s 2.5 seconds. <br />2. Adjust the long door hold open time (time door remains open is response to a ha11 call) to <br />between 5.0 and 8.0 seconds. Measured time is 3.7 seconds. <br />;. Adjust the short door hold open time (time door remains open is response to a car ca11) to <br />between 3.0 and 4.0 seconds. Measured time is 3.6 seconds. <br />4. Adjust the nudging time (time doors remain open when the rays are continually <br />interrupted) to between 20.0 and 25.0 seconds. Measured time is 13 seconds. ~ <br />Items Not Tested: <br />• Operation and leveling with 125% of rated load. <br />• Fire Service operation <br />• Seismic operation <br />• Sound measurement <br />• Motor armature temperatures <br />• Car #3 e~end door hold open time feature <br />