Laserfiche WebLink
077 TFE FACILITY <br /> ITEM BY C-DATE W/O# <br /> 063LTOOIA RBL 8/19/20 00121JPO1 SOLIDS DRAIN SUMP LEVEL TRANSMITTER <br /> ERRATIC...Replaced transmitter and modified DCS overlay display. <br /> 077 EC 5/1/20 00430EC01 REPLACE OLD T8 FLOURESCENT TUBES WITH LED • <br /> REPLACEMENTS.---Removed ballast,rewired tombstones and <br /> installed new LED lamps <br /> 077F1T205A PJS 11/17/20 90909BDW9 METER ELECTRONICS HAVE FAILED. REPLACED <br /> ELECTRONICS AND PROBE WITH CURRENT METER FROM <br /> SAME MANUFACTURER.New single element and transmitter <br /> installed: Metron MTZ-PIT UMF2R, S/N 347471. <br /> SMP077TFE01 RBL 8/5/20 00803LLG1 FRIDGE IS NOT ACHIEVING TEMPERATURE <br /> SETPOINT...Defrosted evaporator. <br /> SMP077TFE01 CLC 10/13/20 01006FJSI VACUUM PUMP MAKING LOUD NOISES---replaced pump with <br /> spare <br /> 101 BARSCREEN FACILITY <br /> ITEM BY C-DATE W/O# <br /> 101 MJN 3/3/20 00127RBL1 LIGHTS IN BAR SCREEN BASEMENT ARE GOING OUT. <br /> REPLACE ALL LAMPS AND RESTRIKE LAMPS----Work <br /> completed by NSE <br /> 101 BJL 2/6/20 00131 KJW 1 MOMENTARY SWITCH FOR WASHER COMPACTOR LIGHTS <br /> IS BROKEN---tightend up switch. <br /> 101 MJN 7/20/20 00612MJN 1 FIXTURE IN BASEMENT OF BARSCREEN IS NOT WORKING <br /> BEACAUSE OF A BROKEN CEILING MOUNT. ORDER AND <br /> REPLACE CEILING MOUNT.---New ceiling mount installed by <br /> NSE . <br /> 101 MJN 8/1/20 007 16BDW8 KEIZER FIRE DISTRICT INSPECTIONS REVEALED THE <br /> FOLLOWING VIOLATION. 1006.1 ILLUMINATION REQUIRED: <br /> REPAIR EGRESS LIGHTING ON HEADWORKS BASEMENT, <br /> EAST WALL. <br /> ELT101Q push to test light has been repaired. <br /> 101 BJL 11/17/20 01026MJN1 MAKE MODIFICATIONS TO ONE RAG BOX FIXTURE TO SEE <br /> IF AN LED LAMP CAN BE INSTALLED.---Completed and works, <br /> may change them all out to LED <br /> 101 BJL 12/2/20 01 127LLG 1 LIGHT SWITCH DOES NOT TURN LIGHT ON.THEY LIGHT <br /> SHWILE SWITCH IS HELD IN THE UP POSITION BUT GO OUT <br /> WHEN SWITCH IS RELEASED.---replaced switch cover. <br /> I01AIT528A CLC 4/29/20 00407CLC1 SENSOR FAILED CALIBRATION---replaced sensor <br /> 101FCV002A MJN 1/21/20 00102JMG1 GATE WOULD NOT CLOSE IN AUTO, WENT TO LOCAL AND <br /> THE GATE CLOSED AFTER REPEATEDLY TOGGLING <br /> SWITCH ON CONTROL PANEL.---believe this may have been <br /> related to the analog input/output card failure.see WO 00115BDW 1 <br /> 101FCV002A MJN 1/21/20 001 15BDW 1 TRIDENT GATE MICROLOGIX PLC INDICATES A MAJOR <br /> ERROR 0379h CODE AND GATE HAS CLOSED.CONTROL <br /> PANEL IS UNRESPONSIVE.---replaced analog input/output card <br /> and reset fault on PLC. Working ok now. <br /> I01FCV004A RBL 8/19/20 00623CJT1 Switched from B channel to A channel. Secured#2 Recycle Gate but • <br /> had DCS alarm"Inf Disch BP GAT2 OVER TORQUE"Alarm.No <br /> Alarm showing on local display. Will not Reset on DCS although <br /> showing closed on local display...Tested ok <br /> Page 16 of 20 <br />