<br /> QUELL SYSTEM
<br /> CLASS II COMMODITIES
<br /> GENERAL GUIDELINES:
<br /> Ultra K17(TY7103)Sprinklers with a 286°F(141°G)temperature rating must be installed in double interlock preaction systems
<br /> or dry systems for the protection of high piled storage occupancies including single,double,and multiple-row rack storage,
<br /> as well as palletized and solid piled storage,of up to Class II commodities as defined by NFPA 13(no open top containers).
<br /> For ceiling only protection(no in-rack sprinklers),the installation criteria is as follows:
<br /> • a minimum deflector to top of storage clearance of 36 inches(0,9 m)
<br /> • a maximum coverage area of 10002(9,3 m7 per sprinkler
<br /> • a minimum coverage area of 80 ft2(7,3 m2)per sprinkler
<br /> • sprinkler spacing criteria:
<br /> 12 feet(3,6 m)maximum for unobstructed and non-combustible obstructed construction
<br /> 10 feet(3,0 m)maximum for combustible obstructed construction
<br /> 8 feet(2,4 m)minimum for all construction
<br /> • water supply duration-90 minutes minimum
<br /> Minimum Sequential Sprinkler
<br /> Maximum Minimum
<br /> Storage Ht./ Design Recommended Opening Times,
<br /> Ceiling Ht., Pressure, No.of Design pelry ry Time Deliveater
<br /> ry Time Sec.lhael
<br /> Ft./Ft. psi SpenklereM. (Operating Time), (Operating Time),
<br /> (Wm) (bar) Rat IAPPendix, Sec.wl SecW 1st 2nd 3rd Lih
<br /> Test No.)
<br /> 20/30(6,1/9,1) 22(1,5) 25(App.B,Ti) 30 9 0 3 6 8
<br /> 25/30(7,6/9,1) 22(1,5) 25(App.B,Ti) 30 9 0 3 6 8
<br /> 20/35(81/10,7) 22(1,5) 25(App.B,Ti) 30 9 0 3 6 8
<br /> 25/36(7,6/10 7) 22(1,5) 25(App.B,TI) 30 9 0 3 6 8
<br /> 4 30/35(9,1/10,7) 22(1,5) 25(App.B,T1) 30 9 0 3 6 8
<br /> 20/40(6,1/12,2) 22(1,5) 25(App.B,Ti) 30 9 0 3 6 8
<br /> 25/40(7,6/12,2) 22(1,5) 25(App.B,T1) 30 9 0 3 6 8
<br /> 30/40(9,1/12,2) 22(1,5) 25(App.B,T1) 30 9 0 3 6 8
<br /> 35/40(10,7/12,2) 22(1,5) 25(App.B,T1) 30 9 0 3 6 8
<br /> 20/45(6,1/13,7) 30(2,1) 25(App.A,T7) 25 9 0 3 6 8
<br /> 25/45(7,6/13,7) 30(2,1) 25(App.A,T7) 25 9 0 3 6 8
<br /> 30/45(9,1/13,7) 30(2,1) 25(App.A,T7) 25 9 0 3 6 8
<br /> 35/45(10,7/13,7) 30(2,1) 25(App.A,T7) 25 9 0 3 6 8
<br /> 40/45(12,2/13,7) 30(2,1) 25(App.A,T6) 25 9 0 3 6 8
<br /> 40/48(12,2/14,6) 30(2,1) 25(App.C) 25 8 0 3 5 7
<br /> Notes:
<br /> a. The minimum recommended number of designsprinklers is to be confirmed with authority having jurisdiction.Refer to the appropr
<br /> iate i to appen-
<br /> dix material.When spinkler coverage areas of 100 tt (9,3 m')are used for all 25 design sprinklers,the resulling designa area is
<br /> 2SanWode(of design
<br /> spunkier coverage areas less than 1001F(9,3 mq are utilized the design area is not be less than 2250112(209 m')', gn
<br /> sprinklers may need to be increased accordingly.
<br /> b.The maximum water delivery time(operating time per SprinkFOr 0)shall be calculated so as to assure the minimum sprinkler design pressure is
<br /> .available at each of the most h draulical demandinglour sprinklers within the noted time(when applyingthe water deliverycalculation enter the
<br /> sequential sprinkleropening times for each of me four sprinklers)
<br /> dnklers).
<br /> mum
<br /> n
<br /> u The minimum water not available at any of tbeeleast hydralime aulicall demanding ng time per plourtsprinklersklshwitin tbe be culated noted line(whe as lo n appyi 9 the ssure the water delivery calculate pressure
<br /> the
<br /> sequential sprinkler opening times for each of the four sprinklersl.
<br /> TABLE A
<br /> HYDRAULIC DESIGN AND WATER DELIVERY(OPERATING TIME)CRITERIA
<br /> TO PROVIDE CEILING ONLY PROTECTION OF CLASS II COMMODITIES