Laserfiche WebLink
April 15, 1992 <br /> <br />APPLICANT= DONALD BORNER ORIGINAL SYSTEM <br />SIT~ NUMBER: 13389 <br /> <br />Your site has been feund suitable for a PRESSURIZED DISTRIBUTION ALTERNATIVE <br />S~WAGB DISPOSAL SYSTEM. The following construction specifications shall apply <br />to the installation of your septic system. <br /> <br /> 1. The ~ptic tank shall have a minimum liquid capacity of 1000 <br /> gallons. <br /> <br />The projected daily sewage flow for this projest is calculated at <br />450~qallons per haY. B&~ed on soil conditions observed on this <br />site, the disposal field will be sized at 7~1 f~et ~er 150 <br />~allons of projected daily sewage flow. A minimum of 225 lineal <br />feet of disposal field will be required for your proposed develop- <br />ment. The disposal t~nohe~ are constructed two (2) feet wide and <br />on minimum ten (10) foot centers and with no line exceeding 125 <br />feet in length. The trenche~ and perforated pi~e are installed <br />level (±1") and contoured to follow the natural ground surface. <br />The disposal field piping is minimum two (2) inch pressure piping, <br />with a minimum 160 psi rating. The sidewalls of the disposal <br />trenches and top of the filter material shall be lined with filter <br />fabric. <br /> <br />Th~ disposal field shall be constructed with equal distribution <br />with a minimum trench depth of 12 inChe_~ and a maximum trench <br />depth of 12 inehe._~. There must be at least ~6 ~nches of backfill <br />over the te~ of the gravel, measured from the natural ground <br />surface. <br /> <br />An effluent lift pump or siphon whioh is sized to provide a <br />minimum residual head of five (8) feet at the most ~istant orifice <br />is required <br /> <br /> A ca~ping fill is required with this system- The ~ystem shall be <br />constructed as indicated on the attached Capping Pill construction detail <br /> <br />This appro=al is site specific to the area tested and the septic system must <br />be located in the immediate area of the test pi:s unless otherwise authorized <br />by this office. A new site evaluation may ba required if the system is <br />proposed for a different area on the property. <br /> <br />SPECIAL CONDITIONS~ <br /> This pressurized distribution system must be constructed within the <br /> im~ediat~ area of the most easterly test pit. <br /> <br />T~IS IS NOT A PERMIT TO INS~a*.~. T~HE SEPTIC SYSTEM. DO NOT INSTALL THE SYSTE~! <br />~II__t~,~,,~.,~L. ID P~R~_~T HAS ~N ISSUED ~ THIS OFFICE. <br /> <br /> <br />